GE C30 Instruction Manual page 316

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 6 of 46)
ADDR
REGISTER NAME
Security (Read Only)
329F
Supervisor alphanumeric password status
Security (Read Only)
32B4
Engineer alphanumeric password status
Security (Read Only)
32C9
Operator alphanumeric password status
Security (Read Only)
32DE
Observer alphanumeric password status
Security (Read Only)
32E9
Reserved for password settings of future roles (63 items)
B
3328
Security status indicator
Security (Read/Write Setting)
3329
Session Lockout
332A
Session Lockout Period
332B
Undefined
332C
Undefined
332E
Undefined
Security Supervisory (Read/Write Setting)
3331
Local Authentication Enable
3332
Supervisor Role Enable
3333
Lock Relay
3334
Factory Service Mode Enable
3335
Failed Authentication Alarm Enable
3336
Firmware Lock Alarm
3337
Settings Lock Alarm
3338
Bypass Access
3339
Encryption
333A
Serial Inactivity Timeout
Security Command (Read/Write Command)
3350
Operator Logoff
3351
Engineer Logoff
3352
Administrator Logoff
3353
Clear Security Data
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
3374
Address 0x3374 reserved for serial logout
Security Reserved Modbus Registers (Read Only)
3375
Address 0x3374 reserved for serial logout
Event recorder actual values (read only)
3400
Events Since Last Clear
3402
Number of Available Events
3404
Event Recorder Last Cleared Date
Event recorder commands (read/write)
3406
Event Recorder Clear Command
DCMA Input Values (Read Only) (24 modules)
34C0
DCMA Inputs 1 Value
34C2
DCMA Inputs 2 Value
34C4
DCMA Inputs 3 Value
34C6
DCMA Inputs 4 Value
34C8
DCMA Inputs 5 Value
34CA
DCMA Inputs 6 Value
34CC
DCMA Inputs 7 Value
34CE
DCMA Inputs 8 Value
34D0
DCMA Inputs 9 Value
B-14
RANGE
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 99
0 to 9999
0 to 1
0 to 4294967295
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
1 to 9999
0 to 1
0 to 1
0 to 1
0 to 1
0 to 9999
0 to 9999
0 to 5
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
-9999999 to 9999999
C30 Controller System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F001
---
1
F618
---
1
F001
min
1
F001
---
1
F126
---
1
F003
---
1
F001
---
1
F126
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F001
---
1
F126
---
1
F126
---
1
F126
---
1
F126
---
1
F001
---
1
F001
---
1
F617
---
1
F003
---
1
F003
---
1
F050
---
1
F126
---
1
F004
---
1
F004
---
1
F004
---
1
F004
---
1
F004
---
1
F004
---
1
F004
---
1
F004
---
1
F004
DEFAULT
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0
0
3
3
0 (No)
0
514
1 (Yes
0 (Disabled)
0 (Disabled)
0 (Disabled)
1 (Enabled)
1 (Enabled)
1 (Enabled)
0 (Disabled)
1 (Enabled)
1
0 (No)
0 (No)
0 (No)
0 (No)
3
3
3 (Engineer)
0
0
0
0 (No)
0
0
0
0
0
0
0
0
0