GE C30 Instruction Manual page 321

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 46)
ADDR
REGISTER NAME
3BC0
Field Output 1 Seal In (6 items)
3BCC
Field Output 1 Events (6 items)
3BD2
...Repeated for Field Contact Output 2
3C14
...Repeated for Field Contact Output 3
3C56
...Repeated for Field Contact Output 4
3C98
...Repeated for Field Contact Output 5
3CDA
...Repeated for Field Contact Output 6
3D1C
...Repeated for Field Contact Output 7
3D5E
...Repeated for Field Contact Output 8
Field Unit Latching Outputs (Read/Write Setting) (8 modules)
3DC7
Field Latching Output 1 ID
3DCD
Field Latching Output 1 Open
3DCF
Field Latching Output 1 Close
3DD1
Field Latching Output 1 Events
3DD2
Field Latching Output 1 Reserved (2 items)
3DD4
...Repeated for Fielding Latching Output 2
3DE1
...Repeated for Field Contact Output 3
3DEE
...Repeated for Field Contact Output 4
3DFB
...Repeated for Field Contact Output 5
3E08
...Repeated for Field Contact Output 6
3E15
...Repeated for Field Contact Output 7
3E22
...Repeated for Field Contact Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 modules)
3E30
Field Shared Output 1 ID
3E36
Field Shared Output 1 Operate
3E38
Field Shared Output 1 Unit Dest 1
3E39
Field Shared Output 1 Channel Dest 1
3E3A
Field Shared Output 1 Unit Dest 2
3E3B
Field Shared Output 1 Channel Dest 2
3E3C
Field Shared Output 1 Events
3E3D
...Repeated for Field Shared Output 2
3E4A
...Repeated for Field Shared Output 3
3E57
...Repeated for Field Shared Output 4
3E64
...Repeated for Field Shared Output 5
3E71
...Repeated for Field Shared Output 6
3E7E
...Repeated for Field Shared Output 7
3E8B
...Repeated for Field Shared Output 8
3E98
...Repeated for Field Shared Output 9
3EA5
...Repeated for Field Shared Output 10
3EB2
...Repeated for Field Shared Output 11
3EBF
...Repeated for Field Shared Output 12
3ECC
...Repeated for Field Shared Output 13
3ED9
...Repeated for Field Shared Output 14
3EE6
...Repeated for Field Shared Output 15
3EF3
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 modules)
3F00
Field Unit RTD 1Name
3F06
Field Unit RTD 1 Origin
3F07
Field Unit RTD 1 Type
3F08
...Repeated for Field Unit RTD 2
3F10
...Repeated for Field Unit RTD 3
3F18
...Repeated for Field Unit RTD 4
3F20
...Repeated for Field Unit RTD 5
GE Multilin
RANGE
0 to 4294967295
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 65535
0 to 4294967295
0 to 8
0 to 15
0 to 8
1 to 15
0 to 1
0 to 1
0 to 1
0 to 2
C30 Controller System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F300
---
1
F102
---
---
F205
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
---
F205
---
1
F300
---
1
F256
---
1
F001
---
1
F256
---
1
F001
---
1
F102
---
1
F205
---
1
F205
---
1
F259
DEFAULT
0
1 (Enabled)
"FLO Ux /LO"
B
0
0
1 (Enabled)
0
"SO 1"
0
0 (none)
1
0 (none)
1
1 (Enabled)
"RTD 1"
"RTD 1"
0 (100 Ohm
Nickel)
B-19