Parameter description
STATUS_OPTS
Index: 15
Access: r, w in O/S
Option:
Default:
STRATEGY
Index: 3
Access: r, w
Default:
TAG_DESC
Index: 2
Access: r, w
Default:
UPDATE_EVT
Index: 29
Access: r
XD_SCALE
Index: 12
Access: r, w in MAN, O/S
Default:
64
EB 8383-1 EN
S
Used to select available status options to determine the treatment and processing of the
status:
Uninitialized
Propagate Fault Backward
Status of the Transducer is passed on to the upstream connected
Block using the status of BKCAL_OUT.
Uninitialized
S
The strategy field can be used to identify grouping of blocks to allow a faster analysis
of the blocks. Enter the same number in the STRATEGY parameter of each block to
group blocks.
0
Note: This data is not checked or processed by the AO Function Block.
S
For entering a user-specific text of max. 32 characters to clearly identify and assign
the block.
No text
D
This alert is generated by any change to the static data, including date and time.
S
Definition of the range (lower range and upper range value) of the engineering unit
and the number of digits behind the decimal point of the manipulated variable (OUT).
Specified in [%], [mm] or [grad].
0.0...100.0 %
Note: On using [%], the value for OUT is scaled based on 100 %. For [mm] (globe
valves) or [grad] (rotary valves), the value currently set in RATED_TRAVEL in the
Transducer Block is scaled as 100 %.