Samson 3787 Mounting And Operating Instructions page 55

Foundation fieldbus positioner
Table of Contents

Advertisement

VALVE_MODEL_NUM
Index: 26
Access: r, w
VALVE_SN
Index: 27
Access: r, w
VALVE_TYPE
Index: 28
Access: r, w
Input:
Default:
XD_CAL_LOC
Index: 29
Access: r, w
XD_CAL_DATE
Index: 30
Access: r, w
XD_CAL_WHO
Index: 31
Access: r, w
XD_ERROR
Index: 11
Access: r
Display:
S
Type/version of the valve associated with the positioner.
S
Serial number of the valve associated with the positioner.
S
Valve type
UNINITIALIZED
Undefined
LINEAR
(Control valve with a straight moving plug, globe valve)
ROTARY
(Control valve with a rotating plug, part-turn, rotary motion)
OTHER
linear
Note: Type 3787 differentiates merely between linear and rotary control valves.
"Undefined" and "other" are treated as globe valves.
S
Location of last calibration.
S
Date of last calibration.
S
The person who carried out the last calibration.
D
Error message of the Transducer Block
NONE (0)
UNSPECIFIED ERROR
GENERAL ERROR
CALIBRATION ERROR
CONFIGURATION ERROR
ELECTRONICS FAILURE
MECHANICAL FAILURE
DATA INTEGRITY ERROR
ALGORITHM ERROR
No error.
(Device not initialized, initialization or zero calibration
running or total valve travel exceeded).
(General device error)
(Zero, internal control loop or initialization error).
(Parameter or characteristic error).
(Checksum error).
Dynamic values outside of range.
Parameter description