Parameter description
TRANSDUCER_STATE
Index: 32
Access: r
Display:
TRANSDUCER_TYPE
Index: 10
Access: r
TRANSM_CODE
Index: 51
Access: r, w
Input:
Input:
TRANSM_LENGTH
Index: 52
Access: r, w
Range:
Default:
TRANSM_PIN_POS
Index: 53
Access: r, w
Input:
Default:
UPDATE_EVT
Index: 7
Access: r
VALVE_MAN_ID
Index: 25
Access: r, w
54
EB 8383-1 EN
D
State of Transducer Block.
SEE ACTUAL MODE OF TRANSDUCER BLOCK
FORCED VENTING ACTIVE
LOWER TRAVEL LIMIT ACTIVE
UPPER TRAVEL LIMIT ACTIVE
END POSITION ACTIVE AT <
END POSITION ACTIVE AT >
S
Type of transducer, here "Standard Advanced Positioner Valve"
S
Transmission code (only for linear actuators with integral positioner attachment)
Determines the size of the travel pick-off when the positioner is integrally attached.
D1, Lever 64 mm
D2, Lever 106 mm
Transmission code (only for rotary actuators)
Maximum opening angle of the selected segment of the cam disk installed.
S90, 90 degrees segment
S120, 120 degrees segment
Note: This parameter has no effect with rotary actuators.
S
Transmission length (only for linear actuators with NAMUR attachment)
Lever length, distance between travel pick-off and pivot of the lever.
0 ... 1023 mm
42 mm
Note: This parameter is only used with linear actuators with NAMUR attachment; it
has no effect on other types of actuators.
S
Transmission pin position (only for linear actuators with NAMUR attachment)
Position of the pin on the lever of the positioner. See marking on the positioner lever.
A
B
A
Note: This parameter is only used with linear actuators with NAMUR attachment; it
has no effect on other types of actuators.
D
This alert is generated by any change to the static data, including date and time.
S
Clear identification of the manufacturer of the valve associated with the positioner.