Parameter description
SELF_CALIB_STATUS
Index: 56
Access: r
Display:
SELF_CALIB_WARNING
Index: 57
Access: r
Display:
SERVO_GAIN_1
Index: 18
Access: r, w
Range:
Default:
SERVO_GAIN_2
Index: 19
Access: r, w
Range:
Default:
SERVO_RATE
Index: 20
Access: r, w
Range:
Default:
52
EB 8383-1 EN
D
Status of sequence started with SELF_CALIB_CMD.
UNDETERMINED
RUNNING
ABORTED
RANGE ERROR
DEFECTIVE MECHANICS / PNEUMATICS
TIMEOUT
PROPORTIONAL RANGE RESTRICTED
RATED TRAVEL OR TRANSMISSION ERROR
MECHANICAL ERROR
PNEUMATICAL ERROR
INITIALIZATION STATUS:
INITIALIZATION STATUS:
NITIALIZATION STATUS:
INITIALIZATION ABORTED DUE TO ACTIVATED FORCED VENTING OPTION
ZERO ERROR
SUCCESSFUL
NO VALID DATA FROM APPLICATION
D
Additional alert messages of the sequence started with SELF_CALIB_CMD
UNDETERMINED
WRONG SELECTION OF RATED TRAVEL OR TRANSMISSION
AIR LEAKAGE OF PNEUMATIC SYSTEM
SUCCESSFUL
NO VALID DATA FROM APPLICATION
S
Proportional-action coefficient for filling
0.01...10.0
0.5
S
Proportional-action coefficient for venting
0.01...10.0
1.2
S
Gain factor of derivative element
0...1
0.12
DETERMINATION OF MECHANICAL STOPS
DETERMINATION OF MINIMUM PULSES
DETERMINATION OF MINIMUM TRANSIT TIMES