Foundation fieldbus positioner
Table of Contents

Advertisement

MANUFAC_ID
Index: 10
Access: r
Display:
MAX_NOTIFY
Index: 31
Access: r
Display
MEMORY_SIZE
Index: 22
Access: r
MIN_CYCLE_T
Index: 21
Access: r
Display:
MODE_BLK
Index: 5
Access: r, w
Display:
NV_CYCLE_T
Index: 23
Access: r
RESTART
Index: 16
Access: r, w
Option:
S
Shows the manufacturer identification number.
0 x 00E099 = SAMSON AG
S
Shows the maximum number of unacknowledged event reports possible.
8
S
Shows available configuration memory in kilobyte.
Note: This parameter is not supported as the function blocks of the Type 3787 are
configured as permanent.
S
Shows time duration of the shortest cycle interval of which the device is capable
(execution time of the AO Function Block 50 ms).
1600 1/32 ms
N
Shows the actual, target, permitted and normal modes of the Resource Block.
AUTO
O/S
The Resource Block supports the following modes:
AUTO
In this mode, the execution of the function blocks is (AO and PID Function
Blocks) granted.
O/S
In this operating mode, the execution of the function blocks is (AO and PID
Function Blocks) is stopped.
These blocks then go into O/S mode.
S
Shows the minimum time interval for copying device data to non-volatile memory.
Note: Non-volatile data are saved directly after being transferred in the Type 3787.
D
Allows a manual restart to be initiated. Several degrees of restart are possible.
RUN
Standard operation
RESOURCE
(is not supported)
DEFAULTS
Device data and connection of the function blocks are reset
to the values determined in the specification.
PROCESSOR
Reset of the device, reboost of the processor.
Parameter description
43