3. INSTALLATION AND OPERATION

3.4 POWER SUPPLY

3.4.1 General
The Searchline Excel gas detector is designed to be operated from a nominal 24V DC supply.
The supply voltage at the terminals must be within the range 18 to 32V.
The unit maximum power consumption and cable lengths are as follows:
Unit Type
Receiver (All ranges)
SR Transmitter,
(Turbo heating enabled)
SR Transmitter,
(Turbo heating disabled)
MR/LR Transmitter,
(Turbo heating enabled)
MR/LR Transmitter,
(Turbo heating disabled)
Notes:
1.
Control room supply voltage assumed to be +24V.
2.
Standard configuration of the Transmitter is with turbo heating enabled.
Terminal sizes: DVC100(M) MK2
DX100(M)
Honeywell Analytics
Junction Box 00780-A-0100
3.4.2 Power Supply Connections - Turbo heating Disabled
When connected as shown in section 3.3.4 Transmitter Connections all ranges of Transmitter
have turbo heating mode enabled.
This means that during conditions of low ambient temperature, additional heating power is
applied to the unit's window to minimise condensation, frosting and snow buildup.
If the application/installation does not require turbo heating, reduced power consumption can
be achieved by disabling this mode.
The turbo heating is disabled by reversing the power supply connections to the Transmitter as
shown in the following diagram. All other connections remain the same.
Maximum Power
Maximum Cable Length
Consumption (W)
Conductors (12 ohms/km) Conductors (7.6 ohms/km)
8
5
3.5
7.5
5.5
2
(m) with 1.5mm
550
900
1,300
600
820
2
2
0.5mm
- 4mm
(20AWG - 12AWG)
0.5mm
2
- 4mm
2
(20AWG - 12AWG)
0.5mm
2
- 6mm
2
(20AWG - 10AWG)
23
Searchline Excel
Maximum Cable Length
2
(m) with 2.5mm
900
1,400
2,000
950
1,300