INSTALLATION
f. The earth bonding arrangement must ensure that the maximum
peak voltage between the unit case earth and any field cable
conductor is less than 350V. Voltages in excess of this can cause
permanent damage to the unit's RFI protection filters.
g. The use of a single, screened cable for each gas detector ensures
maximum screening and minimum crosstalk. Cabling arrangements
which use a single cable for connecting a number of field devices
compromise screening, increase the potential for crosstalk and
prevent implementation of true star earthing.
h. Any electrical interference induced onto the 4 - 20mA loop
conductors by the installation must be kept below the levels
necessary to comply with the general requirements of EN 60079-
29-1 &, IEC 60079-29-1. In practice, this means that
peak noise currents induced on the current loop should be no
greater than ± 0.25mA
j.
The 0V rail of the control card/control system is directly connected
to one side of the 4 - 20mA current sensing resistor. Electrical noise
on this rail is therefore directly connected to the 4 - 20mA input.
In order to avoid additional noise being induced on the 0V rail,
it should not be commoned with the safety earth/ground, which
frequently carries a high level of electrical noise.
k. All electrical equipment connected to the gas detector should
comply with EN61000-6-3 and EN61000-6-2.
l.
The 24V supply should be free from large transients and
fluctuations.
m. The field cabling conductors should have sufficient cross sectional
area to ensure that the minimum supply voltage applied to the gas
detector is 18V at a current of 420mA. This corresponds to a
maximum round loop impedance of 14 ohms for a nominal 24V
system supply.
n. Receivers should not be installed in close proximity to the antennae
of high powered radio, radar and satellite communication
equipment.
11
Installation Guide
Searchline Excel
Open Path Infrared Gas Detector
INSTALLATION
4.3.2 Electrical Installation
1. Isolate all associated power supplies and ensure that they remain OFF
during this procedure.
2. If the units are to be installed with junction boxes other than
OELD or DX100(M) junction boxes, ensure that the boxes:
have M20 cable gland entries for ATEX / IECEx units, or 3/4 NPT
for UL and CSA.
have terminals for 5 wires and an earth.
3. Remove the M20 blanking plugs (if fitted) and attach the Excel
transmitter and receiver cables to their junction box. Fit the locking
rings (if supplied) before terminating the cables in the junction box.
4. Fit approved cable glands to the junction box cable entries, using
sealing washers where necessary to maintain the ingress protection
rating.
5. Fit approved blanking plugs to all unused cable entries.
6. Make appropriate electrical connections as shown in the following
diagrams.
4.3.3 Receiver Connections via OELD
Green/Yellow (Safety/Protective Ground)
Red (+24 Vdc)
Black (0 Vdc)
+24 Vdc in
Field
White (4-20 mA Output)
0 V
Wiring
Blue (RS-485B)
4-20 mA
Orange (RS-485A)
OELD
Note: Using metal cable glands will connect the screen of the cable to the Excel Body.
12
CONTENTS
1. Introduction
2. Safety
3. Mechanical assembly
3.1 General
3.2 Transmitter
3.3 Receiver
3.4 Adjustable Mountings
4. Installation
OELD Operating Instructions
4.1 General
4.2 Mechanical Installation
4.3 Electrical Installation
4.3.1 Electrical Connections
4.3.2 Electrical Installation
4.3.3 Receiver Connections via OELD
4.3.4 Receiver Connections via DX100(M)
4.3.5 Transmitter Connections
4.3.6 Remote Installation Receiver Connections
4.3.7 Transmitter Connections - Turbo Heating Disabled
1
INSTALLATION
4.3.4 Receiver Connections via DX100(M)
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
CABLE SCREEN
The earth bonding arrangement must ensure
CABLE SCREEN
that the maximum peak voltage between the
Modbus A (TB1/6)
Modbus A (TB1/6)
unit case earth and any field cable conductor
Modbus B (TB1/5)
Modbus B (TB1/5)
is less than 350V. Voltages in excess of this
Modbus Drain
Modbus Drain
can cause permanent damage to the unit's RFI
protection filters.
CABLE SCREEN
CABLE SCREEN
+24V (TB2/2)
Note: The Dx100(M) is housed in a metal
+24V (TB2/2)
4-20mA OUT (TB2/3)
4-20mA OUT (TB2/3)
enclosure.
0V (TB2/6)
0V (TB2/6)
EXCEL RECEIVER WIRING
INSTRUMENT (CLEAN)
INSTRUMENT (CLEAN)
WHITE (4-20mA) TB2/3
WHITE (4-20mA) TB2/3
EARTH STAR-POINT
EARTH STAR-POINT
GREEN/YELLOW (EARTH)
GREEN/YELLOW (EARTH)
Same potential as Excel body and conduit.
Same potential as Excel body and conduit
BLACK (0V) TB2/5
BLACK (0V) TB2/5
RED (+24Vdc) TB2/1
RED (+24Vdc) TB2/1
BLUE (B) TB1/2
BLUE (B) TB1/3
ORANGE (A) TB1/2
ORANGE (A) TB1/3
4.3.5 Transmitter Connections
EXCEL
EXCEL
TRANSMITTER
TRANSMITTER
Honeywell Analytics Junction Box
WIRING
JUNCTION BOX
WIRING
00780-A-0100
CABLE SCREEN
CABLE SCREEN
GREEN/YELLOW (EARTH)
GREEN/YELLOW (EARTH)
Same potential as Excel body and conduit
Same potential as Excel body and conduit
RED (+24V)
RED (+24V)
BLACK (0V)
BLACK (0V)
NOTE: FOR DNV VERSIONS, REFER TO THE SEARCHLINE EXCEL TECHNICAL
HANDBOOK FOR SPECIAL INSTRUCTIONS ON THE INSTALLATION,
ALIGNMENT AND COMMISSIONING USING THE MARITIME BRACKET AND
HARDWARE
13
1. INTRODUCTION
2
This guide provides the installation personnel with the basic information
3
necessary to mechanically install the Searchline Excel system units and
make the necessary electrical connections.
4
This guide is not intended to replace the associated Searchline Excel
4
Technical Handbook (2104M0506) which contains the full safety,
4
installation, commissioning, maintenance and fault finding instructions.
4
These procedures assume that consideration of the location and
5
mounting of the system units has already been taken into account in
accordance with the guidelines in the Technical Handbook.
6
The following diagram shows a typical system configuration and
identifies the main parts.
6
6
OELD or DX100(M)
10
(or other junction box)
Mounting plate
10
12
12
13
Mounting bracket
13
14
14
Receiver
Pivot block
Transmitter
Flexible conduit
Monitored
path
5 - 200m
2
INSTALLATION
4.3.6 Remote Installation Receiver Connections
4.3.6.1 Remote installation via OELD - refer to Section 4.3.3
4.3.6.2 Remote installation via DX100(M)
LOCAL JUNCTION BOX
(mounted on Receiver mounting plate)
CABLE SCREEN
EXCEL
EXCEL
GREEN/YELLOW (EARTH)
RECEIVER
RECEIVER
Same potential as Excel body and conduit
Use isolating glands where necessary
ORANGE (A)
BLUE (B)
RED +24V
BLACK (0V)
WHITE (4-20mA)
DX100(M) JUNCTION BOX
DX100(M) JUNCTION BOX
(mounted in a convenient and accessible position)
(mounted in a convenient and accessible position)
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
CABLE SCREEN
CABLE SCREEN
Modbus A (TB1/6)
Modbus A (TB1/6)
Modbus B (TB1/5)
Modbus B (TB1/5)
Modbus Drain
Modbus Drain
CABLE SCREEN
CABLE SCREEN
+24V (TB2/2)
+24V (TB2/2)
4-20mA OUT (TB2/3)
4-20mA OUT (TB2/3)
SAFETY / PROTECTIVE
SAFETY/PROTECTIVE GROUND
GROUND
Where the DX 100(M) is not bonded
Where the DX100(M) is not bonded
to a local safety/protective earth then
0V (TB2/6)
0V (TB2/6)
to a local safety/ protective earth
an external safety/protective earth
then an external safety / protective
needs to be made as shown.
earth needs to be made as shown.
INSTRUMENT (CLEAN)
INSTRUMENT (CLEAN)
EARTH STAR-POINT
EARTH STAR-POINT
CABLE SCREEN
CABLE SCREEN
GREEN/YELLOW (EARTH)
CONTROL
CONTROL
ORANGE (A) TB1/2
BLUE (B) TB1/3
CABINET
CABINET
RED (+24V) TB2/1
RED (+24V) TB2/1
BLACK (0V) TB2/5
CONNECTIONS
CONNECTIONS
BLACK (0V) TB2/5
WHITE (4-20mA) TB2/3
WHITE (4-20mA) TB2/3
SAFETY / PROTECTIVE
SAFETY/PROTECTIVE GROUND
GROUND
Where the DX 100(M) is not bonded
Where the DX100(M) is not bonded
to a local safety/protective earth then
to a local safety/ protective earth
an external safety/protective earth
then an external safety / protective
needs to be made as shown.
earth needs to be made as shown.
EARTH
EARTH
4.3.7 Transmitter Connections - Turbo Heating Disabled
+24V
+24V
0V
0V
EXCEL
EXCEL
Honeywell Analytics Junction Box
TRANSMITTER
TRANSMITTER
part number 00780-A-0100
WIRING
JUNCTION BOX
WIRING
GREEN/YELLOW (EARTH)
GREEN/YELLOW (EARTH)
INSTRUMENT (CLEAN)
Same potential as Excel body and conduit
Same potential as Excel body and conduit
INSTRUMENT (CLEAN)
EARTH STAR-POINT
EARTH STAR-POINT
BLACK (0V)
BLACK (0V)
RED (+24V)
RED (+24V)
Shows wires reversed to
disable turbo heating
The earth bonding arrangement must ensure that the maximum peak voltage between the
unit case earth and any field cable conductor is less than 350V. Voltages in excess of this
can cause permanent damage to the unit's RFI protection filters.
14
Find out more
www.honeywellanalytics.com
Contact Honeywell Analytics:
Europe, Middle East, Africa, India
Life Safety Distribution GmbH
Javastrasse 2
8604 Hegnau
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
India Tel: +91 124 4752700
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
25
405 Barclay Blvd.
Lincolnshire, IL 60069
Honeywell Analytics
USA
Junction Box
Tel: +1 847 955 8200
00780-A-0100 (or
other junction box)
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
7F SangAm IT Tower, 434 Worldcup Buk-ro,
Mapo-gu, Seoul 03922
Korea
Tel: +82-2-69090300
Fax: +82-2-69090328
analytics.ap@honeywell.com
Technical Services
EMEA: HAexpert@honeywell.com
US:
HA.us.service@honeywell.com
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
CABLE SCREEN
CABLE SCREEN
EARTH
EARTH
+24V
+24V
0V
0V
INSTRUMENT (CLEAN)
INSTRUMENT (CLEAN)
EARTH STAR-POINT
EARTH STAR-POINT
Issue 6 07/2017
MAN0558_EMEAI
2104M0510
© 2017 Honeywell Analytics
Please Note:
While every effort has been made to ensure
accuracy in this publication, no responsibility
can be accepted for errors or omissions.
Data may change, as well as legislation and
you are strongly advised to obtain copies
of the most recently issued regulations,
standards and guidelines. This publication is
not intended to form the basis of a contract.

Advertisement

loading

Summary of Contents for Honeywell Searchline Excel

  • Page 1 Searchline Excel system units and make the necessary electrical connections. 3. Mechanical assembly Contact Honeywell Analytics: This guide is not intended to replace the associated Searchline Excel 3.1 General Technical Handbook (2104M0506) which contains the full safety, Europe, Middle East, Africa, India 3.2 Transmitter...
  • Page 2 NOTE: FOR DNV VERSIONS, REFER TO THE SEARCHLINE EXCEL TECHNICAL electrical installation. Each unit needs to mounted to a supporting 1. The Searchline Excel gas detector is certified for and intended for use in potentially HANDBOOK FOR SPECIAL INSTRUCTIONS ON THE INSTALLATION, ALIGNMENT AND hazardous areas.