3. INSTALLATION AND OPERATION
Use a viewing position that ensures that the full circular view is in sight. An ellipse will
appear when slightly off axis.
Caution: do not try to adjust the cross-hairs using the telescope's elevation and windage
adjusters as they have been factory set.
Clamp nuts
Adjustment clamp
(6)
Tighten and loosen each pair of adjustment screws sequentially in the horizontal and
vertical directions until the setting is correct.
(7)
When correctly adjusted, tighten both adjustment screws simultaneously.
Ensure there is minimum movement whilst locking the assembly.
(8)
Check alignment and repeat steps 5 to 7 as necessary.
(9)
Remove the telescope assembly from the unit by reversing the fitting instructions.
(10) Carry out the final commissioning procedures described in the next sub-section.
Adjustment clamp
lock screw (2 off)
Pivot block
adjusting screw
(2 off)
lock screw
(2 off)
Off-axis view
Off-axis view
Mounting bracket
adjusting screw (2 off)
40
Searchline Excel
Clamp nuts
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Pivot block
adjusting screw
(2 off)