MAN0530 Issue 10 - 11/09
2104M0506
3. INSTALLATION AND OPERATION
3.7.5 Commissioning the Gas Detector
This process consists of the following steps:
•
Connect the Handheld Interrogator to the gas detector
•
Power-up the gas detector and check/set the mode of the Interrogator for
operation with the installed Excel gas detector
•
Set the gas detector real-time clock
•
Complete the alignment process
•
Finish up
Connecting the interrogator
Connect the SHC1 Handheld Interrogator to the gas detector in one of the following ways:
•
via a Honeywell Analytics DVC100(M) MK2 or DX100(M) Junction Box - connect the
Interrogator directly to the junction box via its IS socket, e.g.
Distant Excel
Cross-hairs
After alignment
41
unit
ESC
Searchline Excel
Calibrator
Type SHC1