Rectangular Weir (Contracted), P3 = 8 - Siemens OCM III Instruction Manual

Open channel flow meter
Table of Contents

Advertisement

RECTANGULAR WEIR (CONTRACTED), P3 = 8

'U' parameters required *
U0 = crest width b
*
obtain from manufacturer's specifications.
**
calculated by OCM-3. May be viewed by accessing 'U' parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0
For flows that can be calculated by the equation:
q = K x (b - 0.2h) x h
where :
q = flow rate
h = head
K = constant
RATIOMETRIC CALCULATION, P4 = 1
For flows that can be calculated by the equation:
q = q
x (b - 0.2h)/(b - 0.2h
cal
where :
q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01
¤
1.5
¤
) x (h/h
)
cal
cal
OCM III
2.5
72

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents