Vibration Isolators

It is recommended that isolators be used on all upper level
Vibration Isolators
installations or in areas where vibration transmission is a
consideration.
Figure 7: Isolator Locations
4
LB
1
LF
Table 7: Isolator Kit Part Numbers
WGZ-DW Packaged Chiller Isolator Kit Part Numbers
Model Num ber
030-060
Spring-Flex
332320501
332325501
R-I-S
WGZ-DA Remote Condenser Isolator Kit Part Numbers
Model Num ber
030-060
Spring-Flex
332320506
R-I-S
332325504
Table 8: Vibration Isolator Mounting Locations (Packaged Chillers)
Unit
Spring-Flex Mountings
Size
M1
ID-900
WGZ030DW
Green
ID-900
WGZ035DW
Green
ID-900
WGZ040DW
Green
ID-900
WGZ045DW
Green
ID-900
WGZ050DW
Green
ID-900
WGZ055DW
Green
ID-900
WGZ060DW
Green
ID-1350
WGZ070DW
Purple
ID-1350
WGZ080DW
Purple
ID-1800
WGZ090DW
Green
ID-1800
WGZ100DW
Green
28
RB
3
Water
Connections
2
FRF
Control Panel
070-080
90
332320502
332320503
332325502
332325502
070-080
090-115
332320507
332320508
332325501
332325501
M2
M3
M4
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-900
ID-900
ID-900
Green
Green
Green
ID-1350
ID-1350
ID-1350
Purple
Purple
Purple
ID-1350
ID-1350
ID-1350
Purple
Purple
Purple
ID-1800
ID-1800
ID-1800
Green
Green
Green
ID-1800
ID-1800
ID-2400
Green
Green
Gray
Transfer the unit as indicated under "Moving the Unit." In all
cases, set the unit in place and level with a spirit level. When
spring-type isolators are required, install springs running under
the main unit supports.
The unit should be set initially on shims or blocks at the listed
spring free height. When all piping, wiring, flushing, charging,
etc., is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed.
A rubber anti-skid pad should be used under isolators if hold-
down bolts are not used.
Installation of spring isolators requires flexible piping
connections and at least three feet of flexible electrical conduit
to avoid straining piping and transmitting vibration and noise.
Refer to unit dimension drawing for mounting locations.
100-130
150-200
332320504
332320505
332325503
332325503
130
150-200
332320509
332320510
332325501
332325505
R-I-S Mountings
M1
M2
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
Brick Red Brick Red Brick Red Brick Red
M3
M4
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-3
RP-3
Gray
Gray
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
Brow n
Brow n
RP-4
RP-4
IM 1131-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wgz200dwWgz030daWgz200da

Table of Contents