Download Print this page

Ametek DNC-PS700-A10 Operation And Installation Manual page 2

Differential pressure control meter

Advertisement

N a ti o n al C o n tro l s C o rp.
Phone 800-323-2593 • Fax 630-231-1377 • www.nationalcontrols.com
Dustronix PS700-A10 Operation Manual
Table of Contents
Warranty
Important Notice to Users
1.0 DNC-PS700-A10 Overview
3.0 Electrical Hookup
5.0 Alarm Event
6.0 Programming
6.1. Alarm Low Set Point
6.3. Cleaning Low Set Point
6.4. Cleaning High Set Point
6.6. Cleaning Relay
6.7. Unit of Measure
6.8. Security Code
7.0 Specifications
8.0 Default Values
9.0 Displays
10.0
Environmental
Dustronix PS700 Operation Manual
N a ti o n al C o n tro l s C o rp.
Phone 800-323-2593 • Fax 630-231-1377 • www.nationalcontrols.com
WARRANTY
All of National Controls' products are warranted for a period of 1
year against defects and workmanship. Because certain conditions
3
may apply to different product categories, contact the factory for
3
detailed warranty information.
3
IMPORTANT NOTICE TO USERS
4
NCC products are capable of use in a wide array of devices and
4
applications. Any device or system incorporating a NCC product
5
should be designed that, in the event of failure, malfunction, or
5
normal wear of the product, the device or system will become
5
inoperative in a manner which will prevent bodily injury or
5
property damage. In order to keep abreast with the latest
6
technology, National Controls Corporation reserves the right to
6
change components, design, and specifications without notice.
6
7
1.0 DNC-PS700-A10 OVERVIEW
7
The Dustronix PS700 is a Digital/Bargraph Differential Pressure
7
(∆P) Control Meter in the family of Dustronix products, and is
7
designed to interface with NCC dust collector controls as well as
8
other controllers. The PS700 is capable of measuring differential
10
pressure and displaying that value in both analog bargraph and
10
digital displays. Both Hi/Lo Cleaning and Hi/Lo Alarm set points
10
can be programmed, each with relay outputs that can be
programmed either normally open, or normally closed. The
Cleaning relay will change state when the measured pressure
exceeds the High Cleaning Set point, and will return to normal
when the measured pressure goes below the Low Cleaning Set
point. The Alarm relay will change state whenever the measured
pressure is equal to or exceeds the window defined by the High
and Low Alarm Set points, and return to normal when the ∆
pressure falls within the window. The PS700 will accept a 0-10"
pressure input. A 4-20mA output loop is provided from the
internal pressure sensor. A 3-digit security code is also provided
to prevent unauthorized changes. The meter is equipped with non-
volatile memory, which will store all operating parameters when
power is removed.