Notes

9-2 External output function

(1) The function of external output
• The "ON" signal is output when one or more air conditioner are in the ON operation.
• The "Malfunction" signal is output when one or more air conditioner malfunctions.
(2) Specification of external output interface
CN5
Lead wire
No.1
Green
No.2
Black
No.3
Brown

9-3 LAN connection function

When using the LAN connection function, connect the LAN cable to the LAN connector of this device.
* Procure the LAN cable at the site, and use 100 BASE-TX Straight cable.
* For a description of the IP address setting method, refer to section 6 Inital Setting Method.
* LAN is 100 BASE-TX Specification.
CAUTION
Use a security device such as a router when connecting to
the Internet.

10. Specifications

\
Item
Power supply
Temperature
Humidity
Weight
Dimensions (W × H × D)
• Using level signals
• While the Emergency stop contact is ON, operation from both the controller and local
remote controller (ON/OFF only) is prohibited. After the emergency stop is cancelled,
air conditioning units will remain stopped, and they will require manual operation if
they need to be started back up.
• When level signals are used for ON/OFF, operation from both the controller and local
remote controller (ON/OFF only) is prohibited at all times.
• Using pulse signals
• If the operation signal is received during operation, air conditioning units will remain in
operation. (The same is applicable to OFF/Prohibit/Permit.)
• When pulse signals are used, change of ON/OFF, operation mode, temperature
setting, filter sign reset settings will be prohibited from the remote controller.
Description of each terminal
Common (External ground)
ON/OFF
Malfunction/Normal
M-NET Terminal
Controller drive
Operating
Non operating
30 ~ 90 %RH (No condensation)
2.1kg [4.6 lb]
300 × 185 × 70.3 [25.6] mm 11-
*[ ]: indicate the thickness from the wall.
Specification
17VDC~32VDC
24VDC
0 ~ 40°C [32~104°F]
-20 ~ 60°C [-4~140°F]
13
/
× 7-
5
/
× 2-
13
/
16
16
16
– 50 –
LAN
* PAC-SC51KUA supplies the power.
[1-
/
] in
1
16

Advertisement