Mitsubishi Electric AG-150A Instruction Book page 28

Electric air-conditioner network system centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

(6) Save the contents of schedule
4-3-2-3 Setting the current date schedule
Selecting [Schedule Setting] from the main menu on the [Main operation screen] will bring up the schedule setting screen.
Subsequently, selecting [Today] from the sub menu will bring up the current day schedule setting screen. By using this function,
schedule for the current date can be set without having to change the weekly or annual schedule. First select the item to be set, and
then set the schedule.
Note: When the contents of an operation are executed as part of a schedule these contents will continue to be in effect until they are
changed by a schedule or browser etc. Therefore, if you are setting a schedule that is only for a particular day, be sure to set
your schedule in a way that will not impact on the next day's operation.
For example, if you wish to prohibit operations being performed from the remote controller after 17:00, set a Prohibit operation
for 17:00 and set an Enable operation for 23:59.
(1) Select the item to be set.
As with the weekly schedule setting, select the item to be set. (Refer to 4-3-1 (1).)
(2) Set the contents of the schedule
Refer to 4-3-1 (3) for the figure of LOSSNAY and
hot water supply equipment.
(Air Conditioner)
After all the settings have been made, touch the [OK] button to save
the schedule settings.
Touch the [Cancel] button to go back to the previously saved settings
without making any changes.
Touch the schedule content button on the current day schedule
screen to bring up the schedule content setting screen. Make the
settings for the execution time and operation patterns (ON/OFF,
operation mode, setting temperature, airflow direction, fan speed,
remote controller operation prohibition) on the schedule content
setting screen, and then touch the [OK] button. Not all settings need to
be made. The settings for only the operation mode or the setting
temperature, for example, can be made.
Note: When setting a schedule for all groups or for a block, it is
possible to set all operation modes such as Auto mode etc, but
if some targeted air conditioner units do not have such a
function, then those units will not run in the specified mode.
When setting the schedule, consider what functions are
supported by the air conditioner units.
Note: When setting a schedule for all groups or for a block, it is
possible to set prohibit remote controller items individually.
When allowing remote controller operation under K control,
however, all items must be set enable.
Note: When setting a schedule for ventilator units, the temperature
setting is not displayed. Moreover, the prohibit remote
controller operation is simply [ON/OFF].
Note: Only the ON/OFF operation is possible on the general
equipment.
– 26 –

Advertisement

Table of Contents
loading

Table of Contents