External Output Function - Mitsubishi Electric G-50A Instruction Book

Central controller
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

(B) Pulse signal
1Even if the ON signal is input during ON, the status will remain at the ON status.
2When the local remote controller is prohibited, the ON/OFF operation, operation mode selection and tempera-
ture setting from the local remote controller is prohibited.
3Set the pulse width (contact ON time) to 0.5 to 1.0 second.

7 - 2 External output function

(1)The function of external output
•The "ON" signal is output when one or more air conditioner are in the ON operation.
•The "Malfunction" signal is output when one or more air conditioner malfunctions.
(2)Specification of external output interface
CN2
Lead wire
No.1
No.2
No.3
1"ON" signal and "Malfunction" signal will both be output.
Green
Black
Brown
Description of each terminal
Common (0V)
ON/OFF
Malfunction/Normal
– 39 –

Advertisement

Table of Contents
loading

Table of Contents