To access the information on the easy way system, the master-supervisor
must have the following settings:
CAREL master protocol;
baud rate 19200.
Below are the tables of supervisor variables for the components in the
system.

5.1 Access point variable list

par.
description
-
Domain opening status
Enable open/close domain
-
(see command set for variable I12)
-
Device CAREL address
-
Number of sensors presenti
Commands (enabled with D3)
5266
Open network domain for associating the devices
-
5267
Close network domain for associating the devices

5.2 Terminal variable list

par.
description
-
Ambient temperature
-
Ambient humidity (99.9 temperature-only model)
-
Battery level
-
Minimum temperature variation to force transmission
-
Minimum humidity variation to force transmission
-
Temperature set point
-
Humidity set point
-
Indicative wireless signal level
-
Temperature delta in COMFORT
-
Temperature from supervisor if D11=1
-
Humidity from supervisor if D11=1
-
Dead band for temperature calculation algorithm (AUTO mode)
Humidifi cation algorithm diff erential
-
0.0
algorithm disabled
-
Heating/cooling algorithm diff erential
loc 5
Ambient temperature sensor calibration
loc 6
Ambient humidity sensor calibration
loc 4
Temperature delta in Sleep mode (night)
Local temperature sensor alarm
-
0
no temperature sensor alarm
1
temperature sensor alarm
Local humidity sensor alarm
-
0
no humidity sensor alarm
1
humidity sensor alarm
ON/OFF
-
0
terminal off
1
terminal on
Sleep mode status
-
0
instrument not in sleep mode
1
instrument in sleep mode
Occupancy mode status
-
0
deactivated
1
active
Humidifi cation request
-
0
request not active
1
request active
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007

5. SUPERVISOR

min
max
def UOM type
0
1
-
0
1
-
1
15
-
0
60
-
0
65535
-
min
T&H
T
-20.0 -7.0 80.0 55.0
1.0
---
0.0
0.1
1.0
8.0
0.0
-100.0
-5.0
-40.0
1.0
0.0
0.0
1.0
-9.5
-10.0
-5.0
0
0
0
0
0
0
32
index
R/W notes
0= Network closed
-
D
2
R
1= Network open
0= standard operation
-
D
3
R/W
1= enable command I13
-
I
2
R
-
I
9
R
-
I
13
R/W
max
def
UOM type index
T&H
T
--
°C
100
---
--
%rH
100.0
--
%
5.0
1.0
°C
10.0
5.0
%rH
32.0
25.0
°C
100.0
50.0
%rH
-30.0
--
Dbm
5.0
0.0
°C
80.0
0.0
°C
100.0
0.0
%rH
25.0
0.0
°C
25.0
5.0
%rH
10.0
1.0
°C
9.5
0.0
°C
10.0
0.0
%rH
5.0
0.0
°C
1
-
1
-
1
1
1
0
1
0
1
-
Tab. 5.a
R/W notes
A
1
R
A
2
R
A
3
R
A
4
R/W
A
5
R/W
A
6
R/W
A
7
R/W
A
8
R
A
9
R/W
A
10
W
A
11
W
A
12
W
A
13
W
A
14
W
A
15
R/W
A
16
R/W
A
17
R/W
D
4
R
D
5
R
D
6
R/W
D
7
R/W
D
8
R/W
D
9
R