Reset Devices - Carel easy way aria User Manual

Completely wireless carel solution for the management of ambient comfort in buildings
Table of Contents

Advertisement

Repeater
Connecting the repeater to the access point:
Power up the repeater.
Open the domain on the access point (press the button once).
Press the button on the repeater.
All the LED should be on steady.
The repeater is searching for an access point to connect to (all the LEDs
fl ash every 20 s).
The binding operation is successful when only the yellow LED remains
fl ashing.
Now the repeater is connected to the access point.
Note:The binding operation between the repeater and the access
point may fail if:
the distances are large and/or there is infrastructure that prevents
communication between the devices.
The maximum number of repeaters connectable to the access point
has been reached.
Connecting sensor S2 to the system:
OPEN DOMAIN: press the button on the access point and the 3 LEDs
fl ash together.
Wait 20s for the repeater/repeaters installed to receive the domain
open message (all the LEDs fl ash).
In this status, new devices can be connected.
Follow the sensor binding procedure (paragraph 3.4 sensor).
CLOSE DOMAIN: After having connected all the devices, press the
button to close the domain (the LED on the left starts fl ashing).
Note:
the domain closes automatically 15 minutes after last opening.
No address needs to be set on the repeater.
The setup is complete and the system is ready for data communication.
Note: each terminal/sensor should be visible from at least two
devices, either access point or repeater. In the event of a repeater
fault, in this way the terminal/sensor can fi nd an alternative route for
communicating with the access point.
Fig. 3.e

3.5 Reset devices

To reinitialise the devices to the initial purchase status, proceed as
follows.
Access point/Repeater
Important : All the devices previously associated will be removed
from the access point/repeater (no devices connected = 0).
Press the button until the 3 LEDs remain on steady (not fl ashing).
Release the button.
The LEDs will start fl ashing quickly;
the device is reinitialised if after a few seconds the LED on the left
remains on steady.
par. description
min max def UOM typ ind. R/W note
-
Number of sensors
0
present
Sensor
The address of the sensor can only be set again if it has fi rst been
associated with an access point; in the case the connection to the access
point in question will be removed.
press the button on the rear until the LED fl ashes (10 s);
release the button;
the LED will fl ashes quickly;
the device is reinitialised if when pressure the button again the LED
remains on for 15 s.
Note: resetting the terminal/sensor does not eliminate the space
reserved for the terminal inside the access point. Note that, after
resetting the terminal/sensor, the number of devices on the access point
remains unvaried.
par. description
min max def UOM typ ind. R/W note
-
Number of sensors
0
present
13
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007
60
-
I
9
R
60
-
I
9
R
GB

Advertisement

Table of Contents
loading

Table of Contents