5.2 Programming Problems

Causes: The valves will turn on using the "Manual Run" feature but will
not water automatically. Check the following:
Solution:
1) The Rain Stop is active. To reactivate the program schedule, go into the
Main Menu-Rain Stop/Restart and cancel Rain Stop (see Programming,
page XXXXXXXX).
2) Check the date and time on the controller to make sure that it is the same
as the handset.
3) No programming schedules have been entered yet. In Controller Menu,
select program and Setup a Schedule.
4) The programmed runtime of the stations is set to "0" duration. Go into
Controller Menu, select the program and alter runtime.
5) A sensor is hooked up to the system that is inhibiting irrigation or sensor
wires are not connected if sensor added.
6) If the valves operate correctly in a manual run but not in a scheduled
program, check that the following settings are correct:
• Review the programs
• Sensor is active
• Month stop - turn off Month off and Month Selection screens
• Schedule start times, runtimes per program set correctly
7) If a program runs but starts unexpectedly check the schedule settings. If a
new program starts before the old program has completed it will be stacked
to commence later.
8) Make sure there is enough time between the programs and/or start times
to meet your watering time in budget (up to 200% possible)
Causes: No communication
Solution:
1) Check that the controller PVM (solar) panel is not covered. If it has been
covered for an extended period, the controller time will reset.

5.3 The Password has been Changed or Forgotten:

Please call DIG Customer Service with the serial number of the controller.