Input/Output Signal Interfaces - ABB RELION 630 Series Applications Manual

Motor protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 3
REM630 variants
3.2.3
28

Input/output signal interfaces

Table 6:
Interface of binary inputs
Hardware module instance Hardware channel
COM
COM
COM
COM
COM
COM
COM
COM
COM
COM
COM
COM
COM
COM
The outputs of the IED are categorized as power outputs (POx) and signal outputs
(SOx). The power outputs can be used for starting and stopping the motor. The signal
outputs are not heavy-duty outputs. They are used for alarm or signaling purposes.
Table 7:
Interface of binary outputs
Hardware module instance Hardware channel
PSM
PSM
PSM
PSM
PSM
PSM
PSM
PSM
PSM
The IED measures the analog signals needed for protection and measuring functions
via galvanically isolated matching transformers. The matching transformer input
channels 1...4 are intended for current measuring and channels 7...10 for voltage
measuring.
Description
BI1
Circuit breaker closed
BI2
Circuit breaker open
BI3
Circuit breaker truck in
BI4
Circuit breaker truck out
BI5
Earth switch closed
BI6
Earth switch open
BI7
External restart inhibit
BI8
Speed switch
BI9
External trip
BI10
Lockout reset
BI11
Allow emergency start
BI12
Circuit breaker gas pressure
BI13
Circuit breaker spring charged
BI14
MCB open
Description
BO1_PO
Master Trip 1
BO2_PO
Motor start
BO3_PO
Master Trip 2
BO4_PO
Restart enable
BO5_PO
Backup trip
BO6_PO
Not connected
BO7_SO
Common operate
BO8_SO
Common start
BO9_SO
Motor startup
1MRS756785 G
REM630
Application Manual