9.10 "Fault" Messages On The Display/Led - Kaco blueplanet 50.0 TL3 S Operating Instructions Manual

Table of Contents

Advertisement

Maintenance/Troubleshooting

9.10 "Fault" messages on the display/LED

EN
EN
Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are
defined in standards, e.g. VDE0126-1-1. The inverter shuts down if the values exceed or fall below the approved levels.
9.10.1 Display of status and fault messages
Display
FS (fault status)
OS (operating status)
Details regarding the fault or operating status can be found either on the display or in the data that was recorded
through the RS485 interface.
9.10.2 Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician!
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH!
Status
Display
OS 1
Waiting for feed-in
OS 2
Generator voltage too
low
OS 8
Self-test
FS
10
Temperature in
unit too high
OS 11
Measured values
FS 17
Shutting down Pow-
ador-protect
FS
18
Residual current shut-
down
Table 8:
Operating status and fault messages on the display
Page 58
Fault LED (red)
ON
OFF
Explanation
Self-test: The grid parameters
and generator voltage are being
checked.
Insufficient generator voltage and
power,
status before the transition to
night shutdown
Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode.
In case of overheating, the inverter
switches off. Possible causes:
Excessively high ambient tem-
perature,
Fan covered,
Inverter defective.
Power limitation: If the generator power is too high, the inverter
limits itself to the maximum power (e.g. around noon if the gener-
ator capacity is too large).
The activated grid and system pro-
tection has been tripped.
Residual current was detected. The
feed-in was interrupted.
Fault signal relay has switched.
Feed-in was ended due to a fault.
The fault signal relay releases again.
The inverter feeds back into the grid again after a
country-specific time period.
Action
-
-
-
Operating instructions KACO blueplanet 50.0 TL3 S/Basic/M/XL
-
-
-
Cool off the
B
area around the
inverter.
B
Uncover the fans.
E
Notify your author-
ised electrician!
Wait for reactiva-
E
tion.
Notify your author-
ised electrician if
the fault occurs
repeatedly!
Notify your author-
E
ised electrician!