● "Report System Error" has been generated (occurs automatically when compiling in
● The configuration has been loaded.
11.3.11.1

Topology - "Graphic view" tab

Meaning
The Web page in the "Graphic view" tab shows the port interconnection of the components
in the PROFINET IO system.
Example: The expected topology is compared with the actual topology
The figure below shows the view of an expected topology and an actual topology in a STEP
7 project. This is an example of the configuration with an S7-300 CPU and interconnected
PROFINET IO devices. The figure illustrates the possible status information in the graphic
view.
Based on the position numbers, you will find the explanations below the figure. The
explanations can be transferred to any other configuration.
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13
STEP 7)
Note
PROFINET IO system - no display if the line is empty
If no PROFINET IO device is configured in the PROFINET IO system of the CP, there is
no display in the topology view. In this case, the display indicates a disabled topology
display.
Web diagnostics
11.3 Diagnostics pages of the CP
189