Sending process messages by email
8.3 Setting up an e-mail connection
How to configure an e-mail connection
Follow the steps below to configure an e-mail connection in STEP 7:
1. Select the connection type, e-mail connection. The connection partner is initially
unspecified.
2. In the "Properties" parameter group, specify the address parameters of the e-mail server
according to the information in the following table.
Table 8- 2
Connection parameters e-mail connection
Parameters
E-mail server (SMTP)
Default sender name
Using an OPC server as an SMTP server
Instead of an unspecified connection, you can select an OPC server as an SMTP server as
the connection partner. This means that the IP address of the SMTP interface of the PC
station it is entered in the partner's address details.
Note
The PC interface must support the SMTP protocol
The e-mail connection via the OPC server is only created consistently when an interface with
SMTP protocol support is enabled on the PC station. Read the documentation of the module
your using.
140
Description
Address of the mail server via which the e-mails are sent.
The IP address can be specified absolutely or symbolically.
The following applies to symbolic names:
A valid name has 1 to 64 characters of which at least one
character must be a letter.
If one or more "." characters are used, the following constraint also
applies: A valid name has 1 to 3 characters behind the last "."; at
least one of these characters must be a letter.
A symbolic name can only be used if the Internet CP knows the
address of the Domain Name System (DNS). Make an appropriate
entry when configuring the Internet CP in the DNS configuration.
A maximum of 64 characters can be entered.
Specification of an address that is always inserted in the email as
sender address, if the sender specification (FROM parameter) is
empty in the header of the email.
This information is normally irrelevant for delivery of the mail. It is
simply information for the mail recipient. Since some mail servers
do not forward jobs if there is no sender information, it is advisable
to enter information here!
A maximum of 126 characters can be entered.
Note:
Remember that a default sender name must be specified if you
want a test mail to be initiated by special diagnostics.
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13
Example
absolute: 140.80.0.4
symbolic name: t-online.de
Station2.CPU412@xy.factor
y2.de