IBM 11000 VA LCD 5U Installation And Maintenance Manual page 74

Hide thumbs Also See for 11000 VA LCD 5U:
Table of Contents

Advertisement

Table 14. Typical alarms and conditions (continued)
Alarm or condition
Remote Emergency Power Off
(Alarm 12)
Fast Beeping Alarm
Output Overload
(Notice 25)
Slow Intermittent Alarm
Output Overload Level 2
(Alarm 159)
Fast Beeping Alarm
Output Overload Level 3
(Alarm 162)
Fast Beeping Alarm
Battery DC Over Voltage
(Alarm 68)
Fast Beeping Alarm
Charger Failure
(Alarm 34)
Continuous Alarm
Inverter AC Over Voltage
(Alarm 0)
Fast Beeping Alarm
Inverter AC Under Voltage
(Alarm 1)
Fast Beeping Alarm
Rectifier Input Over Current
(Alarm 26)
Fast Beeping Alarm
Inverter Output Over Current
(Alarm 27)
Fast Beeping Alarm
DC Link Over Voltage
(Alarm 28)
Fast Beeping Alarm
DC Link Under Voltage
(Alarm 29)
Fast Beeping Alarm
Inverter Fault
(Alarm 31)
Continuous Alarm
Rectifier Fault
(Alarm 30)
Continuous Alarm
Output Short Circuit
(Alarm 58)
Fast Beeping Alarm
60
11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide
Possible cause
The external contacts in the rear of
the UPS are configured for remote
emergency power-off operation, and
they are activated.
The load level is at or has exceeded
the configurable threshold limit for a
Level 1 Overload condition.
See "Behavior on overload" on page
37.
The load level is >101% and <110%
of the UPS rating.
See "Behavior on overload" on page
37.
The load is >110% of the UPS rating.
See "Behavior on overload" on page
37.
The battery voltage levels have
exceeded the maximum allowable
limits.
A battery charger fault has been
detected.
The UPS has detected abnormally
high output voltage levels.
The UPS has detected abnormally
low output voltage levels.
The UPS has detected that rectifier
input current limits have been
exceeded.
The UPS has detected that the
inverter output current limits have
been exceeded.
The link or rail voltage has exceeded
its upper threshold limit.
The link or rail voltage has dropped
below its lower threshold limit.
The UPS has detected a fault in the
inverter circuit while attempting a
recovery from Bypass mode or Fault
mode.
The UPS has detected a fault in the
rectifier circuit while attempting a
recovery from Bypass mode or Fault
mode.
The UPS has detected an abnormally
low impedance placed on its output
and considers it a short circuit.
Action
The UPS de-energizes the load and
enters Standby mode. For more
information, see "Installing the remote
emergency power-off" on page 14.
The UPS can support the load
indefinitely at this load level.
The alarm clears when the load drops
below 5% of the set point.
Immediately remove some of the
equipment from the UPS.
The alarm clears when the load drops
below 5% of the set point.
Shutdown is imminent.
The alarm clears when the load drops
below 5% of the set point.
The UPS turns off the charger until
the next power recycle. Contact your
service representative.
The UPS turns off the charger until
the next power recycle. Contact your
service representative.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Battery mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
available and supporting the load, or
Fault mode if not.
Contact your service representative.
Contact your service representative.
The UPS shuts down after five line
cycles.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

11000 va ups 3u

Table of Contents