Hard-wiring the UPS input (for licensed electrician only)

CAUTION:
The product might be equipped with a hard-wired power cable. Ensure that a
licensed electrician performs the installation per the national electrical code.
(C022)
The 11000 VA UPS model requires a dedicated branch circuit that meets the
following requirements:
v A breaker that is wall-mounted and readily accessible to the operator:
v A two-pole disconnection device between the UPS output and the load (see the
v 200 - 240 V ac, 50/60 Hz.
v Flexible metal conduit (for ease of service and maintenance).
The following illustration shows the circuit breaker diagram.
To hard-wire the UPS input, complete the following steps:
1. Turn off the utility power at the distribution point where you will connect the
16
11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide
A 63 A (for Europe) or 80 A (for North America) 2-pole circuit breaker to provide
short circuit and overcurrent protection.
(For Europe) The breaker meets the IEC/EN 60934 standard and has a contact
air gap of at least 3 mm.
circuit breaker diagram).
UPS. Be absolutely sure that there is no power.