7. Connect the input and ground wires to the terminal block according to the
8. Replace the terminal block cover.
9. Continue to "UPS initial startup" on page 25.
18
11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide
following illustration and Table 4.
Table 4. UPS wiring specifications
Terminal
Wire functions
position
Input
1
2
3
1
Use the following minimum wire size:
v 8 AWG for equipment grounding wire, 75°C copper wire minimum
v 4 AWG for input line and neutral wires, 75°C copper wire minimum
Terminal position
1 2 3
UPS wire
Terminal wire
function
size rating
Input ground
16 - 35 mm
(8 - 2 AWG)
L2 / Neutral In
L1 In
Tightening
1
torque
2
1.69 Nm (15
inch-pounds)