6.3.6 [009] PGM Types
The output types described in this section can be assigned to alarm controller and output expander module PGMs. Each
alarm controller supports up to 2 or 4 PGMs and can be expanded using HSM2208 output expander and HSM2204 High-
Current output modulemodules. PGM attributes are defined in section "[010] PGM Attributes" on page 85.
[001]-[164] Select PGM
100 – Null PGM
This option deactivates the PGM output
101 – Burglary and Fire Bell Follower
This PGM output follows:
Fire pre-alerts
l
Temporal three fire signal (if enabled)
l
All audible burglary and fire alarms by partition
l
Bell cut-off time
l
Bell squawk conditions
l
Audible exit fault
l
This output activates when the alarm output is active and turns off when the alarm output is silenced. The siren pattern
matches the programmed cadence for the zone that went into alarm. Cadence priority is as follows:
fire alarm cadence
l
CO alarm cadence
l
other alarm cadences
l
The main siren still activates for all alarms.
102 – Delayed Fire and Burglary
This output type operates the same as the Burglary and Fire Bell Follower (PGM type 01), but does not activate until the trans-
mission delay time expires.
When a zone with transmission delay enabled is tripped, the Bell, Regular Fire and Burglary PGMs activate. At the end of the
transmission delay, the delayed Fire and Burglary output activates.
This PGM is usually used to control outdoor sirens. If a false alarm occurs, the user has time to disarm the system before the
external sirens activate.
Note: If a zone alarm occurs but does not follow transmission delay, this PGM activates immediately, even if transmission
delay is active for a different zone alarm.
This output activates for audible exit fault and does not interfere with the operation of any other programmable output.
103 – Sensor Reset [*][7][2]
This output is normally active and deactivates for 5 seconds when a [*][7][2] fire reset command is entered or when an auto
verified fire alarm is detected. This option is used to reset power for latching smoke detectors. The keypad buzzer does not
sound for the 5-second period. See "Smoke Detector Wiring" on page 24 for instructions on wiring smoke detectors.
104 – 2-Wire Smoke
When this PGM is programmed, the onboard PGM functions as an input instead of an output. 2-wire smoke detectors can be
connected to this input, which means that a zone input does not need to be used.
The PGM is also supervised, and a trouble condition is generated if a 2.2KΩ resistor is not present between the PGM ter-
minal and Aux+.