Siemens SIMATIC TP 270 Operating Instructions Manual page 248

Hmi device
Hide thumbs Also See for SIMATIC TP 270:
Table of Contents

Advertisement

Appendix
A.2 System alarms
Number
Effect/cause
280003
A connection is used which requires a function
module in the PLC.
The function block has not replied.
280004
Connection to the PLC is interrupted. There is no
data exchange at present.
290000
The recipe tag could not be read or written to. It is
assigned the start value.
The alarm can be entered in the alarm buffer for up
to four more failed tags, if necessary. After that, the
alarm number 290003 is issued.
290001
An attempt has been made to assign a value to a
recipe tag which is outside the value range
permitted for this type.
The alarm can be entered in the alarm buffer for up
to four more failed tags, if necessary. After that, the
alarm number 290004 is issued.
290002
It is not possible to convert a value from a source
format to a target format.
The alarm can be entered in the alarm buffer for up
to four more failed recipe tags, if necessary. After
that, the alarm number 290005 is issued.
290003
This alarm is issued when alarm number 290000 is
triggered more than five times.
In this case, no further individual alarms are
generated.
290004
This alarm is issued when alarm number 290001 is
triggered more than five times.
In this case, no further individual alarms are
generated.
290005
This alarm is issued when alarm number 290002 is
triggered more than five times.
In this case, no further individual alarms are
generated.
290006
The threshold values configured for the tag have
been violated by values entered.
A-22
Remedy
Check if:
The cable is plugged in
The PLC is OK
The correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
The remedy depends on the error code:
1: The function block must set the COM bit in the
response container.
2: The function block must not set the ERROR bit in the
response container.
3: The function block must respond within the specified
time (timeout).
4: Establish an online connection to the controller.
Check the connection parameters in WinCC flexible.
Check that the cable is plugged in, the PLC is operational
and the correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
Check in the configuration that the address has been set
up in the PLC.
Note the value range for the tag type.
Check the value range or type of the tag.
Check in the configuration that the tag addresses have
been set up in the PLC.
Note the value range for the tag type.
Check the value range or type of the tag.
Note the configured or current threshold value of the tag.
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0