Number
Effect/cause
140015
Incorrect baud rate
or:
incorrect bus parameter (e.g.I)
or:
OP address > I or: incorrect interrupt vector
(interrupt does not arrive at the driver)
140016
Configured interrupt is not supported by the
hardware.
140017
Configured interrupt in use by another driver.
140018
The consistency check was deactivated by
SIMOTION Scout. Only one appropriate note
appears.
140019
SIMOTION Scout loads a new project to the PLC.
Connection to the PLC is interrupted.
140020
The version in the PLC and that in the configuration
(FWX file) do not match.
Connection to the PLC is interrupted.
150000
No additional data is read or written. Possible
causes:
The cable is defective.
The PLC does not respond, is defective, etc.
The connection is established via the wrong
interface.
The system is overloaded.
150001
Connection is
of the interruption has been eliminated.
160000
No additional data is read or written. Possible
causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection has been established via the wrong
interface.
The system is overloaded.
160001
Connection is
of the interruption has been eliminated.
160010
There is no connection to the server because the
server identification (CLS-ID) cannot be
established.
Values cannot be read or written.
160011
There is no connection to the server because the
server identification (CLS-ID) cannot be
established.
Values cannot be read or written.
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
e-established because the cause
!
e-established because the cause
!
Remedy
Correct the incorrect parameters.
Change the interrupt number.
Change the interrupt number.
Activate the consistency check with SIMOTION Scout
again and reload the configuration in the project.
Wait until the end of the reconfiguration.
The following remedies are available:
Load the current version in the PLC using SIMOTION
Scout.
Regenerate the project using WinCC flexible ES, close
WinCC flexible Runtime and restart with a new
configuration.
Check that the cable is plugged in, the PLC is operational
and the correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
-
Check that the cable is plugged in, the PLC is operational
and the correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
-
Check the access rights.
For example, check if
The server name is correct
The computer name is correct
The server is registered
Appendix
A.2 System alarms
A-13