Siemens SIMATIC TP 270 Operating Instructions Manual page 233

Hmi device
Hide thumbs Also See for SIMATIC TP 270:
Table of Contents

Advertisement

Number
Effect/cause
70030
The parameters configured for the system function
are faulty.
The connection to the new PLC was not
established.
70031
The PLC configured in the system function is not an
S7 PLC.
The connection to the new PLC was not
established.
70032
The object configured with this number in the tab
order is not available in the selected screen.
The screen changes but the focus is set to the first
object.
70033
An e-mail cannot be sent because a TCP/IP
connection to the SMTP server no longer exists.
This system alarm is generated only at the first
attempt. All subsequent unsuccessful attempts to
send an e-mail will no longer generate a system
alarm. The alarm is regenerated when an e-mail
has been successfully sent.
The central e-mail component in WinCC flexible
Runtime attempts, in regular intervals (1 minute), to
establish the connection to the SMTP server and to
send the remaining e-mail.
70034
Following a disruption, the TCP/IP connection to
the SMTP server could be re-established.
The queued e-mail are then sent.
70035
The e-mail queue of the central component in
WinCC flexible Runtime responsible for sending e-
mail is full. The e-mail could therefore not be
entered into the queue and therefore not sent.
The cause may be a broken connection to the
SMTP server or an overload resulting from too
much e-mail traffic.
This system alarm is generated only at the first
attempt. The next system alarm is only generated
when at least one e-mail has been successfully
sent to the queue.
70036
No SMTP server for sending e-mail is configured. A
connection to an SMTP server can therefore not be
established and no e-mail can be sent.
The system alarm is generated by WinCC flexible
Runtime the first time an attempt is made to send
an e-mail.
70037
An e-mail cannot be sent for unknown reasons.
The contents of the e-mail are lost.
70038
The SMTP server has rejected sending or
forwarding an e-mail because the domain of the
recipient is unknown to the server or because the
SMTP server requires authentication.
The contents of the e-mail are lost.
70039
The syntax of the e-mail address is incorrect or
contains illegal characters.
The contents of the e-mail are discarded.
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Remedy
Compare the parameters configured for the system
function with the parameters configured for the PLC and
correct them as necessary.
Compare the S7 PLC name parameter configured for the
system function with the parameters configured for the
PLC and correct them as necessary.
Check the number of the tab order and correct it if
necessary.
Check the network connection to the SMTP server and
re-establish it if necessary.
-
Check if
the network connection still exists or
the connection is overloaded (for example, due to
reoccurring system alarms resulting from disruptions).
Configure an SMTP server:
In WinCC flexible Engineering System
using "Device settings > Device Settings".
In the Windows CE operating system
using "Control Panel > Internet Settings > Email > SMTP
Server"
Check the e-mail parameters (recipient, etc.).
Check the domain of the recipient address or deactivate
the authentication on the SMTP server if possible. SMTP
authentication is currently not used in WinCC flexible
Runtime.
Check the e-mail address of the recipient.
Appendix
A.2 System alarms
A-7