INSTALLER'S SETTING OPTIONS
178
NOTE
!
This function setting must be carried out by a certified-technician.

Setting of Function control during group control (air conditioner)

This function enables the control of the common functions or some functions based on the mas-
ter indoor unit during the group control.
● Press and hold 'wireless remote controller signal receiver part' of the remote controller for 3
seconds or longer to enter the installer function.
● At the Code field select the setting code value '19' to enable function control setting during
the group control.
- You can press '▲', '▼' button to change the code value.
● In the Value 1 field, press the '▲', '▼' button set the value for the function control setting dur-
ing the group control, and then press 'Done' button to complete the setting.
- If you do not press 'Done' button, the setting value will not be applied.
h Setting values for the function control during the group control
- 00: only use common function in group control.
- 01: use expanded function which is based on master indoor unit
NOTE
!
• Common functions and some indoor unit master based settings shall be set only for the
group control of the products with the same indoor unit types.
• For the group control of the product groups with different indoor unit types, set it with the
value of '000' and use the existing group control method.
h If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.