INSTALLER'S SETTING OPTIONS
162

ESP setting (air conditioner / Gerneral, DX type ventilator)

This function allows you to set the fan speed step value for each speed rate.
NOTE
!
• If ESP is incorrectly set, it may cause air conditioner malfunction.
• This function must be set by an installation professional.
● Press and hold 'wireless remote controller signal receiver part' of the remote controller for 3
seconds or longer to enter the installer function.
● In the Code field, set the ESP setting value to '03'.
h For ventilation product, code values are divided to '03' supply air and '04' discharge air ESP
setting. Refer to the installer setting code table.
- You can press '▲', '▼' button to change the code value.
● At the Value 1 and Value 2 fields, press the, '▲', '▼' button to select ESP air amount stage and
ESP value, and press 'Done' button to apply the ESP setting.
- If you do not press 'Done' button, your field input value will not be applied.
h ESP setting
- Value 1: ESP fan speed step
- Value 2: ESP value
h ESP setting value input can be 0~255
ESP wind amount stage
wind amount
01
SLOW
02
LOW
03
MED
04
HIGH
05
POWER
<Air conditioner>
NOTE
!
• Be especially careful not to switch ESP values corresponding to each wind amount.
• 'SLOW' and 'POWER' may not be set for some indoor unit products.
• Available ESP value may be different for each product and capacity.

Indoor temperature detection sensor setting (air conditioner)

This function select the temperature sensor to determine the indoor temperature.
● Press and hold 'wireless remote controller signal receiver part' of the remote controller for 3
seconds or longer to enter the installer function.
● At the Code input field select indoor temperature detection sensor setting code value '04'.
- You can press '▲', '▼' button to change the code value.
INSTALLER'S SETTING OPTIONS
163
ESP wind amount stage
wind amount
01
LOW
02
HIGH
03
POWER
<Ventilator>