LG V-NET ACS PREMTA000A Installation And User Manual page 80

Premium wired remote controller
Hide thumbs Also See for V-NET ACS PREMTA000A:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
INSTALLER'S SETTING OPTIONS
158
Code
Setting Mode
Value 1
000 : use basic function only
Function setting in
19
001 : use basic function & some
group control
Master indoor unit function
20
Plasma
21
Heater
000: Not Installed
22
Humidification
001: Installed
23
Elevation grill
24
Ventilation Kit
000: Not installed
25
Auxiliary heater
001: installed-General
002: installed-Duct type
Check indoor unit Ad-
26
dress Number
Use Refrigerant leak-
000 : not use
29
age Sensor
001 : use
Setting temperature
000: 60~86 °F / 16~30 °C
31
range
001: 40~99 °F / 4~37.5 °C
000: use static pressure (code 06)
set value
32
Static Pressure step
001~011: static pressure step
(code 32) set value
000: 0 minute
001: 15 minutes
33
Guard timer
002: 30 minutes
003: 45 minutes
004: 60 minutes
000: Cooling thermal off Fan speed
-Low
Cooling thermal off
35
001: Cooling thermal off Fan OFF
Fan operation
002: Cooling thermal off Fan speed
setting value
Use Primary Heater
000: Cancel primary heater control
36
control
001: use primary heater control
Air conditioner Fan
000: air-conditioner fan off
operation
38
001: air-conditioner fan operate
interlocked with ven-
very low
tilation
000: Use indoor unit auto restart
Indoor unit Auto-Start
39
001: not use indoor unit auto
setting
restart
000: 0 minute
Occupy sensor 'oc-
001: 10 minutes
40
cupy maintain' time
002: 30 minutes
setting
003: 60 minutes
h Some contents may not be displayed depending on the product function.
Setting Value
Value 2
Value 3
<Ventilation product code table>
Setting mode
Code value Functional product
Test Run
1
Central control address setting
2
Air supply ESP
3
Air discharge ESP
4
Product direction
5
Express ventilation priority
6
Remote controller
7
master/ slave setting
Operation master/slave setting
8
Dry contact automatic mode
9
Wind amount fixing
11
Ventilation single
13
humidification
Ventilation heating
14
humidification
Ventilation standard
15
wind amount
h The code value marking may be different for each product.
INSTALLER'S SETTING OPTIONS
Setting value
DX(Direct Ex-
01 : cooling operation
changer) Type
General
00~FF : central control address
<ESP stages>
01 : weak
02 : strong
General/DX Type
03 : very strong
h Same as general air conditioner
products' marking.
01 : normal
General
02 : reverse
01: priority in supply,
General/DX Type
02: priority in discharge
General/DX Type
00:slave, 01:master
DX Type
00:slave, 01:master
DX Type
00:off, 01:set
DX Type
01:variable, 02:fixed
00:function used,
General/DX Type
01:function not used
DX Type
01:automatic, 02:manual
00 : factory ship out value
General Type
11 : 10 % increase
21/22 : 10/20 % decrease
159