Operation; Data Communication - Danfoss AK-PC 560 User Manual

Capacity controller for digital scroll

Advertisement

Operation

Data communication

If the controller is extended with data communication, the opera-
tion can be performed from a system unit. The parameter names
for the functions can be viewed in the right-hand column on
pages 4–10.
The importance of the alarms that are sent can be defined with
the setting: 1 (High), 2 (Medium), 3 (Low) or 0 (No alarm).
Operation via external display
The values will be shown with three digits, and with a setting you
can determine whether the pressures are to be shown in SI units
(°C / bar) or US units (°F / psig.).
There are three options for the display.
P0 is over the neutral zone
P0 is under the neutral zone
1: Relay digital scroll
2: Relay comp. 2
3: Relay comp. 3
.
.
.
EKA 165
10: Capacity form the
digital scroll
EKA 163
EKA 164
The buttons on the display
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the
column with parameter codes. Find the parameter code you want
to change and push the middle button. When you have changed
the value, save the new value by once more pushing the middle
button.
AK-PC 560
Manual RS8GE202 © Danfoss 01-2016
EKA 165
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will
be shown briefly in the display. (If regulation is based only on the
condensation pressure, the display will always show Pc).
During normal operation the light-emitting diodes in the display
will indicate where regulation is taking place.
Second highest :
Over neutral zone
"None"
:
Neutral zone
Second lowest :
Under neutral zone
The other LEDs on the display will show the functions that are
active:
• Relays for compressors
• The capacity can be read from the digital scroll compressor
• Relays for fans
• Input signals for the digital inputs
• The optimization LED will light up when the reference is 2 K or
more over the set point.
EKA 163
If the condensation pressure is to be shown constantly, a display
without operating keys can be connected.
EKA 164
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will be
shown briefly in the display.
Like the EKA 165, the LEDs in the display will show where the
regulation is located.
Or short:
1. Push the upper button (long push) until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push the middle button until the setting value is shown
4. Push one of the buttons and select the new value
5. Push the middle button again to conclude the setting
( A brief pushing will show the active alarm codes. See page 17.)