Menu Survey - Danfoss AK-PC 560 User Manual

Capacity controller for digital scroll

Advertisement

Menu survey

Sequence
1. o61 must be set as the first parameter. This parameter determines which of the four operating interfaces (application mode) are
activated. This must be set via the display keys. It cannot be set via data communication. (Active functions are shown below in shaded
fields.)
2. Quick- start
To get the system up and running quickly so that cooling can be commenced, start it by setting the following parameters (these pa-
rameters can only be set when the regulation is stopped, r12=0): r23, r28, c08, c16, c29, o06, o30, o75, o76 and finally r12=1.
3. Once the regulation is under way, you can go through the other parameters and adjust them in situ.
Function
Normal display
Shows P0 in EKA 165 (display with buttons)
Shows Pc in EKA 163
P0 reference
Neutral zone
Correction of signal from P0 sensor
Select view; SI or US. 0=SI (bar /°C), 1=US (Psig /°F)
Start/Stop of regulation
Reference offset for P0 (see also r27)
Set regulation set point for P0
Shows total P0 reference
( r23 + various displacements)
Limitation: P0 reference max. value
(also applies to regulation with reference displacement)
Limitation: P0 reference min. value
(also applies to regulation with reference displacement)
Displacement of P0 (ON=active "r13")
Pc reference
Set regulation set point for Pc
Shows total Pc reference
Limitation: Pc reference max. value
Limitation: Pc reference min. value
Correction of signal from Pc sensor
Pc reference variation. 1 and 2 are PI-regulation
1: Fixed reference. "r28" is used
2: Variable reference. Outdoor temperature (Sc3) included in the refer-
ence
3: As 1, but with P-regulation (Xp-band)
4: As 2, but with P-regulation (Xp-band)
Reference offset for Pc
The mean temperature difference across the condenser at maximum
load (dim tm K)
The mean temperature difference across the condenser at the lowest
relevant compressor capacity (min tm K)
Capacity
Min. ON time for relays
Min. time period between cutins of same relay
Definition of regulation mode
1: Sequential (step mode / FILO)
2: Cyclic (step mode / FIFO)
Definition of compressor connections.
See options on page 11.
Definition of condenser:
1-8: Total number of fan relays or voltage step on the voltage output
9: Only via analog output and start of frequency converter
10: Not used
11- 18: Total number of fan relays which are to be connected with alter-
nating start-up.
Cut in compressor capacity with manual control. See also "c32"
Manual control of compressor capacity (when ON, the value in "c31" will
be used)
14
Manual RS8GE202 © Danfoss 01-2016
o61 =
Para-
Min.
meter
1
2
-
°C
P
-
°C
P
r01
0.1°C / 0.1 bar
r04
-50°C /-5.0 bar
r05
0
r12
OFF
r13
-50°C / -5.0 bar
r23
-99°C / -1 bar
r24
r25
-99°C / -1.0 bar
r26
-99°C / -1.0 bar
r27
OFF
r28
-25°C / 0.0 bar
r29
r30
-99.9°C / -0.0 bar 99.9°C/ 130.0bar 55.0°C / 60.0 bar
r31
-99.9°C / 0.0 bar
r32
-50°C / -5.0 bar
r33
1
r34
-50°C / -5.0 bar
r35
3.0
r56
3.0
c01
0 min
c07
2 min.
c08
1
c16
1
c29
0/OFF
c31
0%
c32
OFF (0)
SW: 1.0x
Max.
Factory
setting
°C / bar
°C / bar
20°C /5.0 bar
4.0°C / 0.4 bar
50°C / 5.0 bar
0.0
1
0
ON
OFF
50°C / 5.0 bar
0.0
30°C / 60.0 bar
0.0°C / 3.5 bar
°C / bar
30°C / 60.0 bar
30.0°C / 40.0 bar
30°C / 40.0 bar
-99.9°C / -1.0 bar
ON
OFF
75°C / 110.0 bar 35°C / 15.0 bar
°C / bar
99.9°C / 60.0 bar -99.9°C / 0.0 bar
50°C / 5.0 bar
0.0
4
1
50°C / 5.0 bar
0.0
50.0
10.0
50.0
8.0
30 min.
0
60 min
2
2
1
7
1
18
0
100%
0
ON (1)
OFF (0)
Fortsættes
AK-PC 560