The controller can give the following messages
E1
Error
Fault in controller
message
Regulation is outside the range, or the control
E2
signal is defective
Alarm
A2
Low P0
message
A11
Refrigerant not selected
A17
High Pc
A19
Compressor 1 error (29)
A20
Compressor 2 error (31)
A21
Compressor 3 error (32)
A22
Compressor 4 error (33)
A23
Compressor 5 error (34)
A24
Compressor 6 error (35)
A25
Compressor 7 error (36)
Saux discharge gas temperature to high . Digital
A27
scroll is stopped
A28
DI 1 alarm. Terminal 46 interrupted
A29
DI 2 alarm. Terminal 47 interrupted
A30
DI 3 alarm. Terminal 49 interrupted
A31
DI 4 alarm. Terminal 50 interrupted
A32
DI 5 alarm. Terminal 52 interrupted
A34
Fan alarm. There is no signal on DI1 input
A45
Regulation stopped
S0
Status
Regulation
message
S2
Wait for "c01"
S5
Wait for "c07"
Refrigeration stopped by the internal or external
S10
start/stop function
S25
Manual control of outputs
Safety cutout.
S34
Setting A30 is exceeded or all safety inputs (29-
36) are open
Access code is required before you have access to
PS
Info
the settings
AK-PC 560
The actual compressors
safety circuit is
interrupted.
That is to say the signal
is missing on one of the
terminals 29-36
Manual RS8GE202 © Danfoss 01-2016
Messages can be brought up on the display by briefly pressing
the uppermost key. If there is more than one alarm, they can be
scrolled through
Factory setting
If you need to return to the factory-set values, it can be done in
this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as
you reconnect the supply voltage
17