Data
Supply voltage
24 V a.c. +/-15% 50/60 Hz, 5 VA
2 pcs. Pressure transmitters type AKS 32R
3 pcs. temperature sensor input for Pt 1000
Input signal
ohm/0°C
(With NTC and a fixed resistor on Saux, the meas-
uring range becomes 80-140°C.)
1 pcs. for Start/stop of regulation
7 pcs. for monitoring of safety circuits
Digitale input from
3 pcs. for alarm function
contact function.
2 pcs. for alarm function or for displacement of
references
Relay output for
7 pcs. SPST
capacity regulation
AKD start/stop relæ
1 pcs. SPST
Digital output for
Solid State
scroll unloader
Alarm relay
1 pcs. SPDT
Voltage output
0-10 V d.c. Max. 5 mA, Ri min. 2.2 kohm
EKA 163
Display outputs
EKA 165 (164)
Possible to connect a data communication
Data communication
module
0 - 55°C, during operation
-40 - 70°C, during transport
Environments
20 - 80% Rh, not condensing
No shock influence / vibrations
Enclosure
IP 20
Weight
0.4 kg
Mounting
DIN rail or on wall
Terminals
max. 2.5 mm
EU Low voltage Directive and EMC demands re
CE-marking complied with.
Approvals
LVD-tested acc. to EN 60730-1 and EN 60730-2-9
EMC-tested acc. to EN61000-6-2 and 3
Pressure transmitter / temperature sensor
Please refer to catalogue RK0YG...
Capacitive load
The relays cannot be used for the direct connection of capacitive loads
such as LEDs and on/off control of EC motors.
All loads with a switch mode power supply must be connected with a suit-
able contactor or similar.
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to
malfunctions of the control system, and ultimately lead to a plant break-
down.
Every possible safeguard is incorporated into our products to prevent this.
However, a wrong installation, for example, could still present problems.
Electronic controls are no substitute for normal, good engineering prac-
tice.
Danfoss will not be responsible for any goods, or plant components, dam-
aged as a result of the above defects. It is the installer's responsibility to
check the installation thoroughly, and to fit the necessary safety devices.
Special reference is made to the necessity of signals to the controller when
the compressor is stopped and to the need of liquid receivers before the
compressors.
Your local Danfoss agent will be pleased to assist with further advice, etc.
AK-PC 560
AC-1: 3 A (ohmic)
AC-15: 2 A (inductive)
DO1 - DO8 are low voltage
24 V a.c. Imax. = 500mA
Imin. = 70 mA.
Leak <4mA
AC-1: 6 A (ohmic)
AC-15: 3 (inductive)
Pc display
Operation, P0 display and
LED
multicore
2
Manual RS8GE202 © Danfoss 01-2016
Ordering
Type
AK-PC 560
Capacity controller for digital scroll
EKA 163B
Display unit
EKA 164B
Display unit with operation buttons
Display unit with operation buttons
EKA 165
and light-emitting diodes for input and
output
Cable for display unit 2 m, 1 pcs.
Cable for display unit 6 m, 1 pcs.
EKA 175
Data communication module, RS 485
EKA 178B
Data communication module, MOD-bus
Data communication module, LON RS
EKA 174
485, with galvanic separation (recom-
mended when output 0-10 V is used)
Dimensions
AK-PC 560
Display type EKA 163 / EKA 164
Display type EKA 165
Function
Code no.
084B8013
084B8574
084B8575
084B8573
084B7298
084B7299
084B8579
084B8571
084B7124
Only for front mounting (IP 40)
Only connection via plugs
19