Applying Power To The Drive - Allen-Bradley PowerFlex 700S Quick Start Manual

Frequency ac drive
Hide thumbs Also See for PowerFlex 700S:
Table of Contents

Advertisement

30
DRIVE
DRIVE
4
ENABLE
SYNCHLINK

Applying Power to the Drive

The remainder of this procedure requires that a Human Interface Module
(HIM) be installed. If an operator interface is not available, remote devices
should be used to start-up the drive.
PWR (Power)
1
2
STS (Status)
3
❏ 6. Apply AC power and control voltages to the drive. Examine the Power
(PWR) LED.
Table N Drive Status Indicator Descriptions
#
Name
Color
State
PWR
Green
Steady
(Power)
STS
Green
Flashing
(Status)
Steady
Yellow
Flashing
Steady
Red
Flashing
Steady
Red /
Flashing
Yellow
Alternately
PORT
Refer to the
MOD
Communication
NET A
Adapter User Manual
NET B
SYNCHLINK Green
Steady
Green
Flashing
Red
Flashing
ENABLE
Green
On
Green
Off
Description
Illuminates when power is applied to the drive.
Drive ready, but not running & no faults are present.
Drive running, no faults are present.
When running, a type 2 (non-configurable) alarm condition exists,
drive continues to run. When stopped, a start inhibit exists and the
drive cannot be started.
A type 1 (user configurable) alarm condition exists, but drive
continues to run.
A fault has occurred.
A non-resettable fault has occurred.
The drive is in flash recovery mode. The only operation permitted is
flash upgrade.
Status of DPI port internal communications (if present).
Status of communications module (when installed).
Status of network (if connected).
Status of secondary network (if connected).
The module is configured as the time keeper.
or
The module is configured as a follower and synchronization is
complete.
The follower(s) are not synchronized with the time keeper.
The module is configured as a time master on SynchLink and has
received time information from another time master on SynchLink.
The drive's enable input is high.
The drive's enable input is low.