Frame 5
➋
POWER TERMINAL RATINGS
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
17
GROUND TERMINAL RATINGS (PE)
2
WIRE RANGE: 6-1/0 AWG (16-35 MM
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
21
OUTPUT
➌
➊
Fan VA Rating - Common Bus Only
Frame Fan Voltage (120V or 240V)
5
100 VA
6
138 VA
Figure 8 Power Terminal Block Location, Cont'd
Phase Selection
Jumper
Optional
Communications
Module
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
9
Fan Voltage
INPUT AC
1
Frame 5 & 6 utilize a transformer to match the input line voltage to the internal fan voltage. If you line voltage is dif-
ferent then the voltage class specified on the drive nameplate, it may be necessary to change the transformer taps. The
taps are shown in the inserts of frames 5 & 6.
Common Bus drives require user supplied 120V or 240V to power the cooling fans. Power source is connected between
"0V AC" and the terminal corresponding to your source voltage.
Line Type
➋
Spare
Spare
1
690 Volt Tap
600 Volt Tap
480 Volt Tap
400 Volt Tap
➊
➍
Frame 6
Optional
Communications
Module
➍
➌
22-10
AWG
BR2
BR1
DC+
DC–
5.3 IN-LB
(0.6 N-M)
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
USE 75 C
COPPER WIRE
ONLY
TORQUE
T1
T2
T3
L1
L2
52 IN-LB
(6 N-M)
OUTPUT
INPUT
17
L3