28
Analog I/O
Connection Example
Analog Outputs -
+/-10V DC
Used to drive analog
meters displaying speed
and current
Input/Output
Connection Example
Primary Encoder
Primary Encoder - using internal power supply
Interface -
Supports 12V DC
differential encoders with
internal power supply.
5V DC differential
encoders require
external power supply
and special jumper
settings.
Used as primary closed
loop speed feedback
TB1 - Row B (Bottom)
Output #1
Motor
Speed
6
+
-
5
4
3
+
-
2
1
Table M Encoder Wiring Example
TB2 - Row T (Top)
Using Analog Out 1, -10V to + 10V to meter Motor
RPM and direction:
Send the data to the Analog Output
Par 815 [Anlg Out1 Real] (the destination) linked to
Par 300 [Motor Spd Fdbk] (the source)
Scale the Output to the source parameter
Par 817 [Anlg Out1 Scale] = 175 (Par 4 [Motor NP
RPM] = 1750 / 10V)
Output #2
Using Analog Out 2, -10V to + 10V to meter Motor
Motor
Current:
Current
Send the data to the Analog Output
Par 820 [Anlg Out2 Real] (the destination) linked to
Par 308 [Output Current] (the source)
Scale the Output to the source parameter
Par 822 [Anlg Out2 Scale] = xx (Par 2 [Motor NP
FLA] / 10 V Output)
Required Parameter Changes
Using Encoder 0 as speed feedback:
Par 222 [Motor Fdkbk Sel] = 0 "Encoder 0" (default)
Par 232 [Encoder0 PPR] = Pulses/Rev for installed
encoder