Table 1.2 Rating Of Bypass Input Circuit Breaker - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 80/100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

!
NOTE
This UPS does not include a Bypass input circuit breaker (MCCB) to protect
the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field
supplied and installed. Recommended Breaker (MCCB)'s Specifications are
as follows:
Rating of Bypass Input Circuit Breaker
TABLE 1.2
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
80
100
160
225
300
500
750
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed.
The overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.6.
Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be
referred as "CB2".
G9000 Installation and Operation Manual
WARNING 4
480
96
480
120
480
192
480
271
480
361
480
601
480
902
Breaker (A)
125
150
250
350
500
800
1200
5