APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 7 of 60)
ADDR
REGISTER NAME
Bus Actuals (Read Only) (2 modules)
2500
Bus Differential IA Magnitude
2502
Bus Differential IA Angle
2503
Bus Differential IB Magnitude
2505
Bus Differential IB Angle
2506
Bus Differential IC Magnitude
2508
Bus Differential IC Angle
2509
Bus Differential Rest IA Magnitude
250B
Bus Differential Rest IA Angle
250C
Bus Differential Rest IB Magnitude
250E
Bus Differential Rest IB Angle
250F
Bus Differential Rest IC Magnitude
2511
Bus Differential Rest IC Angle
2515
Bus Maximum CT Primary
2517
Reserved (9 items)
2520
...Repeated for module number 2
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2620
Remote Double-Point Status Input 1 Device
2621
Remote Double-Point Status Input 1 Item
2622
Remote Double-Point Status Input 1 Name
2628
Remote Double-Point Status Input 1 Events
2629
... Repeated for Double-Point Status Input 2
2632
... Repeated for Double-Point Status Input 3
263B
... Repeated for Double-Point Status Input 4
2644
... Repeated for Double-Point Status Input 5
IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 modules)
26B0
IEC 61850 GGIO5 uinteger Input 1 Operand
26B1
IEC 61850 GGIO5 uinteger Input 2 Operand
26B2
IEC 61850 GGIO5 uinteger Input 3 Operand
26B3
IEC 61850 GGIO5 uinteger Input 4 Operand
26B4
IEC 61850 GGIO5 uinteger Input 5 Operand
26B5
IEC 61850 GGIO5 uinteger Input 6 Operand
26B6
IEC 61850 GGIO5 uinteger Input 7 Operand
26B7
IEC 61850 GGIO5 uinteger Input 8 Operand
26B8
IEC 61850 GGIO5 uinteger Input 9 Operand
26B9
IEC 61850 GGIO5 uinteger Input 10 Operand
26BA
IEC 61850 GGIO5 uinteger Input 11 Operand
26BB
IEC 61850 GGIO5 uinteger Input 12 Operand
26BC
IEC 61850 GGIO5 uinteger Input 13 Operand
26BD
IEC 61850 GGIO5 uinteger Input 14 Operand
26BE
IEC 61850 GGIO5 uinteger Input 15 Operand
26BF
IEC 61850 GGIO5 uinteger Input 16 Operand
IEC 61850 Received Integers (Read Only Actual Values) (16 modules)
26F0
IEC 61850 Received uinteger 1
26F2
IEC 61850 Received uinteger 2
26F4
IEC 61850 Received uinteger 3
26F6
IEC 61850 Received uinteger 4
26F8
IEC 61850 Received uinteger 5
26FA
IEC 61850 Received uinteger 6
GE Multilin
RANGE
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 50000
---
1 to 32
0 to 64
1 to 64
0 to 1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
---
1
F060
---
---
F001
---
1
F001
---
1
F606
---
1
F205
---
1
F102
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
---
F612
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
DEFAULT
0
0
0
0
0
0
0
0
0
B
0
0
0
1
0
1
0 (None)
"RemDPS Ip
1"
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
B-15

Advertisement