GE B30 UR Series Instruction Manual page 352

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

7.2 TARGETS
Description of problem: Module hardware failure detected.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed module
(for example, F8L).
IEC 61850 DATA SET:
LLN0 GOOSE# Error
Latched target message: No.
Description of problem: A data item in a configurable GOOSE data set is not supported by the B30 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the GOOSE data set are supported by the B30. The EnerVista UR Setup soft-
ware will list the valid items. An IEC61850 client will also show which nodes are available for the B30.
IEC 61850 DATA SET:
LLN0 BR# Error
Latched target message: No.
Description of problem: A data item in a configurable report data set is not supported by the B30 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the configurable report data set are supported by the B30. The EnerVista UR
Setup software will list the valid items. An IEC61850 client will also show which nodes are available for the B30.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is not functioning.
How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec-
onds if the problem persists
What to do: Return the power supply module to GE Digital Energy for battery replacement. To instead dispose of the
battery and power supply module, see the battery disposal information at the beginning of this manual.
7
MAINTENANCE ALERT:
Direct I/O Ring Break
Latched target message: No.
Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
How often the test is performed: Every second
What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
Latched target message: No.
Description of problem: A bad IRIG-B input signal has been detected.
How often the test is performed: Monitored whenever an IRIG-B signal is received.
What to do: Ensure the following:
The IRIG-B cable is properly connected.
7-6
.
.
.
.
B30 Bus Differential System
7 COMMANDS AND TARGETS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents