GE B30 UR Series Instruction Manual page 465

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 45 of 60)
ADDR
REGISTER NAME
IEC 61850 XSWI Configuration (Read/Write Command) (24 modules)
B372
Command to Clear XSWI OpCnt (Operation
Counter)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400
Number of Status Indications in GGIO1
B402
IEC 61850 GGIO1 Indication FlexLogic operands
(128 items)
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function
(GoEna)
B5A1
IEC 61850 Configurable GOOSE ID
B5C2
Configurable GOOSE Destination MAC Address
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit
Priority
B5C6
IEC 61850 Configurable GOOSE VLAN ID
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
B5C8
IEC 61850 Configurable GOOSE ConfRev
(Configuration Revision)
B5CA
IEC 61850 Configurable GOOSE Retransmission
Curve
B5CB
Configurable GOOSE Dataset Items for
Transmission
(64 items)
B60B
...Repeated for module number 2
B676
...Repeated for module number 3
B6E1
...Repeated for module number 4
B74C
...Repeated for module number 5
B7B7
...Repeated for module number 6
B822
...Repeated for module number 7
B88D
...Repeated for module number 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 modules)
B900
Configurable GOOSE Dataset Items for Reception
(32 items)
B920
...Repeated for module number 2
B940
...Repeated for module number 3
B960
...Repeated for module number 4
B980
...Repeated for module number 5
B9A0
...Repeated for module number 6
B9C0
...Repeated for module number 7
B9E0
...Repeated for module number 8
BA00
...Repeated for module number 9
BA20
...Repeated for module number 10
BA40
...Repeated for module number 11
BA60
...Repeated for module number 12
BA80
...Repeated for module number 13
BAA0
...Repeated for module number 14
BAC0
...Repeated for module number 15
BAE0
...Repeated for module number 16
Contact Inputs (Read/Write Setting) (96 modules)
BB00
Contact Input 1 Name
BB06
Contact Input 1 Events
BB07
Contact Input 1 Debounce Time
GE Multilin
RANGE
0 to 1
8 to 128
0 to 4294967295
0 to 1
---
---
0 to 7
0 to 4095
0 to 16383
1 to 4294967295
0 to 3
0 to 1008
0 to 197
---
0 to 1
0 to 16
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F126
---
8
F001
---
1
F300
---
1
F102
---
---
F209
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F611
---
1
F616
---
1
F233
---
---
F205
---
1
F102
ms
0.5
F001
DEFAULT
0 (No)
8
0
1 (Enabled)
"GOOSEOut_
B
x_"
0
4
0
0
1
3 (Relaxed)
0 (None)
0 (None)
"Cont Ip 1"
0 (Disabled)
20
B-53