Advertisement

5.6 GROUPED ELEMENTS
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE
b) GROUND INSTANTANEOUS OVERCURRENT (ANSI 50G, IEC PIOC)

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND IOC1
5
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
5-138
SETTING
GROUND TOC1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
GROUND TOC1
AND
SOURCE:
IG
SETTING
GROUND TOC1
BLOCK:
Off = 0
Figure 5–55: GROUND TOC1 SCHEME LOGIC
SETTING GROUP 1(6)
GROUND IOC1
FUNCTION: Disabled
GROUND IOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
GROUND IOC1
MESSAGE
PICKUP:
GROUND IOC1 PICKUP
MESSAGE
DELAY:
GROUND IOC1 RESET
MESSAGE
DELAY:
GROUND IOC1 BLOCK:
MESSAGE
Off
GROUND IOC1
MESSAGE
TARGET: Self-reset
GROUND IOC1
MESSAGE
EVENTS: Disabled
B30 Bus Differential System
SETTINGS
GROUND TOC1
INPUT:
GROUND TOC1
PICKUP:
GROUND TOC1
CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1
RESET:
RUN
IG ≥ PICKUP
t
I

GROUND CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 30.000 pu in steps of 0.001
1.000 pu
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: FlexLogic operand
Range: Self-reset, Latched
Range: Disabled, Enabled
5 SETTINGS
FLEXLOGIC OPERANDS
GROUND TOC1 PKP
GROUND TOC1 DPO
GROUND TOC1 OP
827036A3.VSD

GROUND IOC1(6)
,
Disabled
GE Multilin