6.2.3.2

Information on configuration type "-"

Restriction
This configuration is not approved.
6.2.3.3

Information on configuration type "A"

Restriction
If process mode is activated for an OS on the ES, simultaneous OS engineering can only be
performed for this activated OS.
6.2.3.4

Information on configuration type "B"

Restrictions
● No additional installation of an OS client is necessary because the OS workstation is already
included in the standard configuration "Engineering Station".
● A PC station cannot be concurrently used as an engineering station and an OS client.
During configuration, process mode of the OS client must be terminated and vice versa.
Notes on configuration
● You need to configure a separate OS client in SIMATIC Manager for this OS workstation.
● You cannot and do not have to load the OS client project.
Notes on process mode
● The SIMATIC Manager must be closed when the client project is opened. Otherwise the
OS client takes its server data from the engineering station.
● Activate the OS client:
1. Open WinCC Explorer.
2. Select the OS client project.
3. Activate process mode.
PCS 7 - PC Configuration (V8.2)
Installation Manual, 03/2016, A5E36200050-AB
6.2 Appendix B - Approved configurations on a PC station
Appendices
149