4.3.1.4 GlobalBusStateField for PROFINET IO

FP7 Fieldbus Master Units Technical Manual
ErrEvent Explanation
210
No database.
212
Faulty reading of a
database.
220
Host watchdog er-
ror.
The following error numbers are valid for the error event if "Error remote
address" is not equal to 255.
ErrEvent Explanation
30
Guarding failed.
31
Node has changed its state
and is no longer operational.
32
Sequence error in guarding
protocol.
33
No response to a configured
remote frame PDO.
34
No response of the node while
being configured.
35
The node profile number con-
figured in the master differs
from the actual node profile
number.
36
The device type configured in
the master differs from the
actual node device type.
37
Unknown SDO response re-
ceived.
38
Length indicator of received
SDO message does not equal
8.
39
Node not handled. Node
stopped.
Source of
Recommendation
error
Project plan-
Download database again.
ning
Device
Download database again.
Host pro-
Check user program or watchdog
gram
timer.
Source of
Recommendation
error
Node
Check whether node is con-
nected.
Node
Reset node.
Node
Reset node.
Node
Check whether node can
handle remote frames.
Node
Check whether node is con-
nected and operational.
Project
Check the supported profile
planning
number of the node: I/O,
encoder, etc.
Project
Check the supported ser-
planning
vices of the node.
Node
Node not compatible with
CiA protocol specification.
Node
Node not compatible with
CiA protocol specification.
Device
Activated auto-clear mode or
host is not ready.
Programming information
37