FP7 Fieldbus Master Units Technical Manual
ErrEvent Explanation
ters.
57
Faulty slave parameter value
in data file.
58
Double slave address.
59
Projected send process data
offset of participant's address
outside allowable range of
0-255.
60
Projected receive process data
offset of participant's address
outside allowable range of
0-255.
61
Slaves' data areas overlapping
for send process data.
62
Slaves' data areas overlapping
for receive process data.
63
Unknown process data hand-
shake.
64
Free RAM exceeded.
65
Faulty slave parameter data
sets.
202
No segment for treatment
free.
212
Faulty reading of database.
213
Structure surrender to operat-
ing system faulty.
220
Software watchdog error.
221
No data acknowledgement in
process data handshake mode
0.
222
Master in auto-clear mode.
225
No further segments.
The following error numbers are valid for the error event if "Error remote
address" is not equal to 255.
ErrEvent Explanation
2
Station reports
overflow.
3
Request function of
master not activat-
ed in the station.
9
No answer even
though slave must
respond.
17
No response from
station.
Source
Recommendation
of error
planning
Project
Contact technical support.
planning
Project
Check projected addresses.
planning
Project
Check projected addresses.
planning
Project
Check projected addresses.
planning
Project
Check projected addresses.
planning
Project
Check projected addresses.
planning
Warm
Check warm start parame-
start
ters.
FMU
Contact technical support.
Project
Contact technical support.
planning
FMU
Contact technical support.
FMU
Download database again.
FMU
Contact technical support.
Host
Check host program.
Host
Host program did not
acknowledge the last hand-
shake in time.
Slave
Auto-clear mode was acti-
vated because one slave
was missing during runtime.
FMU
Contact technical support.
Source of
Recommendation
error
Master
Check length of configured slave con-
telegram
figuration or parameter data.
Master
Check slave if PROFIBUS DP norm
telegram
compatible..
Slave
Check configuration data of the station
and compare it with the physical I/O
data length.
Slave
Check bus cable. Check bus address of
slave.
Programming information