Programming information
34
ErrEvent Explanation
61
Size of the additional
table for predefined
master-slave connec-
tions is corrupt.
62
Size of predefined
master-slave I/O con-
figuration table is cor-
rupt.
63
Predefined mas-
ter-slave I/O configura-
tion does not corre-
spond to the additional
table.
64
Size indicator of pa-
rameter data table is
corrupt.
65
Number of inputs de-
clared in the additional
table does not corre-
spond to the number in
the I/O configuration
table.
66
Number of outputs
declared in the addi-
tional table does not
correspond to the
number in the I/O con-
figuration table.
67
Unknown data type in
I/O configuration de-
tected.
68
Data type of a defined
I/O unit in a connection
does not correspond
with the defined data
size.
69
Output address config-
ured for one unit ex-
ceeds the possible ad-
dress range of 3584
bytes.
70
Input address config-
ured for one unit ex-
ceeds the possible ad-
dress range of 3584
bytes.
71
One predefined connec-
tion type is unknown.
72
Multiple connections
defined in parallel.
73
The value configured
for the expected packet
rate value configured is
Source of error
Recommendation
Configuration
Download error in the
current database. Con-
tact technical support.
Configuration
Download error in the
current database. Con-
tact technical support.
Configuration
Number of I/O units and
the number of config-
ured offset addresses
are different.
Configuration
Value of size indicator
too small.
Configuration
Each entry in the I/O
configuration must have
only one entry in the
additional table.
Configuration
Each entry in the I/O
configuration must have
only one entry in the
additional table.
Configuration
Data types supported:
BOOL, BYTE, WORD,
DWORD and STRING
only.
Configuration
The following types and
size are valid:
Configuration
The process data image
is limited to 3584 bytes.
Configuration
The process data image
is limited to 3584 bytes.
Configuration
Support of cyclic, polled,
change of state, or bit
strobe connections only.
Configuration
Supports only one type
of connection to one
device.
Configuration
The value for the ex-
pected packet rate must
be larger than the pro-
FP7 Fieldbus Master Units Technical Manual
BOOLEAN = 1 byte
Unit 8 = 1 byte
Unit 16 = 2 bytes
Unit 32 = 4 bytes